Overview

The device described in this manual is an uninterruptible power supply (UPS) system, specifically the Infosec M5T series. This series includes models with various power ratings (10k, 15k, 20k, 30k, 40k, 60k kVA) and voltage configurations (HV for 380/400/415V and LV for 208/220V). The M5T series offers both standard and long-run models, with long-run models (WOB/S versions) designed to operate without internal batteries.

Function Description:

The UPS system provides continuous power to connected loads, protecting them from power fluctuations, outages, and other electrical disturbances. It operates in various modes, including AC mode (normal operation), Battery mode (during power outages), and Bypass mode (supplying power directly from the mains). The system is designed for commercial and industrial applications.

Key functions include:

  • Power Conversion: Converts incoming AC power to DC to charge batteries and then back to stable AC power for the load.
  • Battery Backup: Provides power from internal or external batteries during mains failures, ensuring uninterrupted operation of critical equipment.
  • Bypass Operation: Can supply power directly from the mains to the load, either automatically or manually, in case of UPS fault or overload.
  • Constant Voltage Constant Frequency (CVCF) Mode: Ensures a stable output voltage and frequency, independent of input variations.
  • ECO Mode: An energy-saving mode that allows the UPS to operate with higher efficiency by utilizing the bypass line when mains power is stable.
  • Parallel System Capability: Certain models (10k, 15k, 20k kVA HV and 10kVA LV) can be configured in parallel to increase capacity or redundancy.
  • Communication and Monitoring: Equipped with RS-232, USB, and an intelligent slot for SNMP or RS485 cards, allowing for local and remote monitoring and management via software like Infopower. Dry contact ports are also available for external signals and alarm reporting.
  • Emergency Power Off (EPO): A safety feature that immediately cuts off the UPS output in an emergency.

Important Technical Specifications:

Capacity:

  • HV Models: 10kVA/10kW, 15kVA/15kW, 20kVA/20kW, 30kVA/30kW, 40kVA/40kW, 60kVA/60kW
  • LV Models: 10kVA/10kW, 15kVA/15kW, 20kVA/20kW, 30kVA/30kW

Input:

  • Voltage Range (HV): Low Line Loss: 110 VAC(Ph-N) ± 3% at 50% Load; 176 VAC(Ph-N) ± 3% at 100% Load. High Line Loss: 300 VAC(L-N) ± 3% at 50% Load; 276 VAC(L-N) ± 3% at 100% Load.
  • Voltage Range (LV): Low Line Loss: 70 VAC(Ph-N) ± 3% at 50% Load; 88 VAC(Ph-N) ± 3% at 100% Load. High Line Loss: 156 VAC(L-N) ± 3% at 50% Load; 146 VAC(L-N) ± 3% at 100% Load.
  • Frequency Range: 46Hz ~ 54Hz (50Hz system); 56Hz ~ 64Hz (60Hz system).
  • Phase: 3 Phase with Neutral.
  • Power Factor: ≥ 0.99 at 100% Load.

Output:

  • Voltage (HV): 3 x 360*/380/400/415 VAC (3Ph+N) or 208*/220/230/240 VAC (Ph-N).
  • Voltage (LV): 3 x 208/220 VAC (3Ph+N) or 120/127 VAC (Ph+N).
  • AC Voltage Regulation: ± 1%.
  • Frequency Range (Synchronized): 46Hz ~ 54Hz (50Hz system); 56Hz ~ 64Hz (60Hz system).
  • Frequency Range (Battery Mode): 50Hz ± 0.1Hz or 60Hz ± 0.1Hz.
  • Overload Capacity (AC Mode): 100%~110%: 60min; 110%~125%: 10min; 125%~150%: 1min; >150%: immediately.
  • Harmonic Distortion: ≤ 2% @ 100% Linear Load; ≤ 5% @ 100% Non-linear Load.
  • Transfer Time (Line to Battery/Inverter to Bypass): 0 ms.
  • Transfer Time (Inverter to ECO): <10 ms.

Efficiency:

  • AC Mode: 95.5% (HV), 93.5% (LV).
  • ECO Mode: 98.5%.
  • Battery Mode: 94.5% (HV), 92.5% (LV).

Battery:

  • Type: 12V/9Ah or 12V/7Ah.
  • Numbers (Standard Model): (10+10)pcs, (16+16)pcs, or (16+16)pcs x 2 strings (HV); (8+8)pcs or (8+8)pcs x 4 strings (LV).
  • Recharge Time: 9 hours to recover to 90% capacity.
  • Charging Current (max): 1.0A ± 10% (Recommended) to 1.0~12.0A (Adjustable).
  • Charging Voltage: +/-136.5 VDC ± 1% (HV); +/-109 VCC ± 1% (LV).

Physical:

  • Dimensions (D x W x H): 626 x 250 x 826 mm or 815 x 300 x 1000 mm.
  • Net Weight (Standard Model): 105-245 kg (HV); 125-243 kg (LV).
  • Net Weight (Long-run Model): 30-87 kg (HV); 45-87 kg (LV).

Environment:

  • Operation Temperature: 0 ~ 40°C (battery life decreases above 25°C).
  • Operation Humidity: <95% non-condensing.
  • Operation Altitude: <1000m (power derated 1% per 100m above 1000m).
  • Acoustic Noise Level: Less than 58dB to 70dB at 1 meter, depending on model.

Usage Features:

  • LCD Panel: Provides a user-friendly interface with five sub-menus: Control, Measure, Setting, Information, and Data Log.
  • Control Menu: Allows users to turn the UPS on/off, initiate battery tests, mute alarms, and manage the charger. In parallel systems, it also allows units to exit the parallel configuration.
  • Measure Menu: Displays real-time values for line voltage, inverter voltage, bypass voltage, output voltage, output power (W and VA), input power (W and VA), input/output current, battery voltage, bus voltage, charging/discharging current, and internal temperatures.
  • Setting Menu: Configures UPS parameters, including language, input source (utility/generator), output voltage/frequency, CVCF mode, bypass forbid, neutral line check, ISO compensation, bypass UPS off status, bypass voltage/frequency ranges, ECO mode settings, battery warning voltage, shutdown voltage, battery AH, and battery groups. Advanced settings require a password for qualified technicians.
  • Information Menu: Displays basic UPS information such as MCU/DSP versions, serial number, manufacturer, service contact details, parallel status (PAR State, PAR ID), customer code, and dynamic password settings.
  • Data Log Menu: Records warning and fault information with date, time, code, type, and description.
  • Battery Test: Can be initiated manually or through monitoring software to check battery status.
  • Auto Restart: Configurable feature to automatically restart the UPS after a shutdown due to low battery, once utility power is restored.
  • Shutdown Delay/Restore Delay: Allows setting delays for UPS shutdown and automatic restart.
  • 3/3 to 3/1 Model Conversion: Specific models (10k-20k kVA) can be reconfigured from 3-phase input/3-phase output to 3-phase input/1-phase output by qualified personnel.

Maintenance Features:

  • Qualified Personnel: All repairs and maintenance must be performed by qualified service personnel due to hazardous voltages.
  • Safety Precautions: Strict adherence to safety guidelines is emphasized, including disconnecting batteries, verifying absence of dangerous voltage, and using insulated tools.
  • Battery Management: Recommendations for battery replacement by qualified technicians, proper disposal, and precautions against electric shock and short circuits. Battery parameters like AH capacity and groups can be configured.
  • Battery Study/Initialization: Functions to calibrate backup time estimation and initialize virtual battery capacity, especially after battery replacement.
  • Temperature Compensation: Adjusts charging voltage based on battery temperature.
  • Self-Test Function: Allows the UPS to perform an internal self-test to diagnose potential issues. This function is effective for HV systems and requires disconnecting loads and utility first.
  • Troubleshooting Guide: A comprehensive table is provided to help users identify symptoms, possible causes, and remedies for common UPS issues.
  • Storage Guidelines: Instructions for charging the UPS before storage, recommended storage conditions (cool, dry, upright), and periodic battery recharging schedules based on ambient temperature.
  • Fuse Replacement: Fuses must only be replaced with identical types and amperages to prevent fire hazards.
  • No Disassembly: Users are explicitly warned not to disassemble the UPS system.

INFOSEC UPS SYSTEM M5T Series Specifications

General IconGeneral
BrandINFOSEC UPS SYSTEM
ModelM5T Series
CategoryUPS