EasyManua.ls Logo

Ingersoll-Rand 1200 - User Manual

Ingersoll-Rand 1200
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
NIRVANA CYCLING REFRIGERATED DRYER
MODELS 1000-1600
OPERATORS MANUAL
C.C.N. : 80442791
DATE : DECEMBER 2006
REV. : A
Ensure that the operator reads and understands the
decals and consults the manuals before maintenance
or operation.
Ensure that the Operation and Maintenance manual is
not removed permanently from the machine.
Ensure that maintenance personnel are adequately
trained, competent and have read the Maintenance
Manuals.
a

Other manuals for Ingersoll-Rand 1200

Questions and Answers

  • R
    Robert GrantAug 18, 2025
    Why is there a high pressure drop across my Ingersoll-Rand Dryer?
    • K
      kdanielsAug 18, 2025
      A high pressure drop across your Ingersoll-Rand Dryer can occur for several reasons. First, ensure that the inlet and outlet valves are completely open. If not, open them fully. Blocked inlet and outlet filters can also cause this issue, so change the filter elements. Other potential causes include a stuck compressor relay/contactor, which would require replacing the relay/contactor, or a bad microprocessor control relay, which would also require replacement. Inspect the probe and check readings against an independent source (e.g., temperature analyzer/pyrometer/ice bath) both in the exchanger well and to ambient if the probe is not completely in the thermal well. If the problem persists, turn the dryer off and consult your local distributor.
  • S
    Stephen LozanoAug 21, 2025
    What should I do if my Ingersoll-Rand 1200 displays an unrealistic temperature?
    • H
      hendersonjohnAug 22, 2025
      If your Ingersoll-Rand Dryer is showing an unrealistic temperature, start by inspecting the probe cable and terminal connection to ensure they are secure. A loose connection or a defective probe can cause this issue. If the connections are good, the probe itself may be defective and need replacing.
  • J
    Janice NavarroAug 25, 2025
    How to fix erratic temperature readings on my Ingersoll-Rand 1200?
    • C
      Curtis SmallAug 25, 2025
      To address erratic or inaccurate temperature readings on your Ingersoll-Rand Dryer, begin by inspecting the probe to ensure it is completely in the thermal well. Also, check the readings against an independent source, such as a temperature analyzer, pyrometer, or ice bath, both in the temperature well and ambient. If the probe placement and external readings seem correct, the probe itself may be defective and require replacement.
  • M
    Mike BrownAug 27, 2025
    What causes an unrealistic pressure display on my Ingersoll-Rand 1200?
    • D
      Dennis DiazAug 27, 2025
      An unrealistic pressure display on your Ingersoll-Rand Dryer can be caused by a transducer issue. Inspect the transducer cable and terminal connection to ensure they are properly connected. If the connections are secure, the transducer itself may be defective and need to be replaced.
  • M
    Michael GonzalezAug 30, 2025
    What to do if my Ingersoll-Rand 1200 Dryer controller display appears to be malfunctioning?
    • C
      chrishigginsAug 30, 2025
      If the controller display on your Ingersoll-Rand Dryer appears to be malfunctioning, first check the fuses to see if any are blown. If the fuses are intact, contact your local distributor for further assistance, as it may indicate a board failure.
  • W
    William PorterSep 2, 2025
    Why is there air bleeding from the condensate drain outlet port of my Ingersoll-Rand Dryer?
    • S
      Scott RobersonSep 2, 2025
      If you notice air bleeding from the condensate drain outlet port of your Ingersoll-Rand Dryer, it could be due to debris trapped under the seal. Try pressing and holding the test button to clear it, which will open the drain valve. If the issue persists, the seal may be damaged and need replacing with a Service Kit.
  • K
    Kim DanielsSep 5, 2025
    What to do if the condensate drain doesn't fire on my Ingersoll-Rand 1200 Dryer?
    • A
      abeardSep 5, 2025
      If the condensate drain on your Ingersoll-Rand Dryer isn't firing, start by checking that the installation is in accordance with this manual and revise it accordingly. If the inlet/outlet pipe internal diameter is too small, causing an air-lock or back pressure, replace it with larger diameter piping. If there is excessive use of bends/elbows in the inlet/outlet pipe work causing air-lock/back pressure, reduce the amount of bends and elbows. If the outlet pipe is too long/too high causing back pressure, reconfigure the condensate piping. If more than one condensate source is connected, providing an alternative path for condensate, reroute the condensate to eliminate the secondary path and install check valves as required.
  • T
    tonydeckerSep 8, 2025
    What does it mean if the condensate drain LED is off on my Ingersoll-Rand 1200?
    • H
      heatherhallSep 8, 2025
      If the condensate drain LED is off on your Ingersoll-Rand Dryer, check the power supply. Press the test button for a minimum of 2 seconds and observe. Locate and eliminate any supply fault.
  • K
    Kevin MatthewsSep 12, 2025
    What to do if the condensate drain bowl of my Ingersoll-Rand Dryer doesn't fill and seems air-locked?
    • S
      sarahnavarroSep 12, 2025
      If the condensate drain bowl on your Ingersoll-Rand Dryer doesn't seem to fill with condensate and appears air-locked, and you're using the bottom inlet, ensure the top port is used as an air bleed. Connect the top inlet to a higher point in the system; this will function as an air bleed for the drain.
  • A
    anita89Nov 14, 2025
    What to do if there is moisture downstream from my Ingersoll-Rand Dryer?
    • K
      Karen JordanNov 14, 2025
      If you notice moisture downstream from your Ingersoll-Rand Dryer, several factors could be the cause. First, a defective service unit can cause condensate drain failure, so consider replacing the service unit. Excessive flow can also be a factor; check the inlet and outlet pressure and the system design capacity and correct any issues causing excessive flow. Ensure the dryer by-pass valve is completely closed. Check the power supply and fuses/circuit breakers to ensure the dryer is receiving power. High suction pressure can also cause moisture, so check and clean the condenser. If the suction pressure gauge reads 0 psig, there may be a refrigerant leak; turn the dryer off and contact your distributor. If the compressor isn't running but the fan is, inspect and clean the condenser. High amb...

Summary

Receiving, Inspection, and Safety Precautions

General Safety and Operation Precautions

Essential safety rules and precautions to observe during operation and maintenance of the dryer.

Principles of Operation: Core Systems

Air System Description

Describes how compressed air interacts with dryer components from inlet to outlet.

Moisture Removal System Details

Details the operation of the zero-air-loss condensate drain and its sensing mechanism.

Principles of Operation: Advanced Systems

Refrigeration System Function

Describes the R-22 closed-loop system including evaporator, compressor, condenser, and expansion valve.

Dryer Settings and Alarm Management

Alarm Functions and Descriptions

Details various alarms detected by the control, their displays, set points, and impact on dryer operation.

Dryer Start Modes and Installation

Installation and Initial Start-Up Procedures

Electrical Connections and Start-Up Sequence

Electrical Connection Details

Details how to make customer electrical connections at the terminal connections box on the dryer.

Initial Start-Up Procedures

Provides initial startup procedures, including water valve for water-cooled models and crankcase heater warm-up.

Start-Up Sequence Steps

Outlines the sequence of events when applying power, including LCD panel illumination and delay countdowns.

Scheduled Maintenance Procedures

Technician Mode Operations

Entering Technician Mode

Provides the keystroke sequence to enter the protected Technician Mode for advanced parameter manipulation.

Technician Mode: Alarm List

Accessing the Alarm List

Explains how to access and view the list of the most recent 20 alarm conditions for troubleshooting.

Troubleshooting Guide

Problem;Action Guide

A guide to identify common problems, their symptoms, possible causes, and corrective actions.

Overview

The Ingersoll Rand Nirvana Cycling Refrigerated Dryer Models 1000-1600 are designed to remove moisture from compressed air by cooling the air temperature to between 36° and 40°F (2 and 4°C). This process causes water vapors to condense into liquid droplets, which can then be easily removed from the air. The dryer utilizes an Air System, a Moisture Removal System, a Refrigeration System, a Thermal Mass Circulating System, and a Control System to achieve this.

Function Description

The dryer operates by directing hot, saturated air from the compressor into a precooler/reheater. Here, the air temperature is reduced by the cool, dry air exiting the air/moisture separator. This precooling allows for the use of a smaller refrigeration system. The air then moves into the chiller section, where it is further cooled to the desired dew point by a thermal mass fluid. The temperature of this thermal mass fluid is maintained by the refrigeration circuit and its controls. The air continues to the separator, where moisture is removed. The cool, dry air then returns to the precooler/reheater to be heated by the incoming moist hot air. The air exiting the reheater portion of the dryer should be approximately 15°-20°F lower than the inlet air temperature under standard conditions at full rated flow.

The Moisture Removal System employs zero-air-loss condensate drains to discharge condensed moisture and lubricants from the compressed air. This drain system uses a unique sensing method to determine the condensate level in the drain bowl. A transducer continuously sends a signal 50 times per second. Once the condensate level reaches a predetermined point, a signal is sent to the no-loss drain valve, which opens to remove condensate at a rate of up to 80 gallons per hour. The drain also features a test button for manual operation, which illuminates an LED to indicate "POWER ON" and goes off when the drain valve is operated by the transducer or manual test.

The Refrigeration System uses a compressor to circulate refrigerant. The compressor status (ON/OFF) is displayed on the Microprocessor Control. The system also monitors discharge and suction pressures, as well as suction temperature, to ensure optimal performance and to determine the superheat of the refrigerant. The condenser, which can be air-cooled or water-cooled, helps to dissipate heat from the refrigerant. Fan motors are used in air-cooled condensers to facilitate heat exchange.

The Thermal Mass Circulating System uses a circulating pump to move the thermal mass fluid through the chiller. The pump operates continuously in Nirvana Cycling™ dryers, and the compressor cycles on and off based on the chiller temperature.

Usage Features

The dryer is equipped with a Microprocessor Control that provides a user-friendly interface. When power is supplied, the control illuminates and defaults to "Standby" mode, displaying "Press ON." The keypad functions include:

  • ON: Places the dryer "On Line" and energizes the glycol pump. The compressor operates based on temperature.
  • OFF: Places the dryer "Off Line," stopping all automatic functions, including circulating pump operation.
  • SELECT DISPLAY: Allows the user to cycle through available displays. The last selected display remains as the default.
  • +/-: Used to increase or decrease set point values. Values cycle through a fixed range and allow entering negative numbers in FACTORY MODE.
  • TEST: Manually activates the no-loss drain valve.
  • RESET: Clears local alarm indications and de-energizes the remote alarm contact. If the alarm condition persists, it returns after the alarm inhibit time expires.
  • SET: Permits adjustment of parameters in TECHNICIAN and FACTORY MODES. In CUSTOMER MODE, it allows users to back through displays.
  • ENTER: Used to accept changed parameters and set point values.

The Microprocessor Control displays various system parameters, including:

  • Chiller Temperature (CHLLR TEMP): The temperature of the thermal mass fluid in degrees Fahrenheit.
  • Compressor Status (CMPRSSR): Indicates if the refrigeration compressor is "ON" or "OFF."
  • Discharge Pressure (P disch): The discharge pressure of the refrigeration system in psig.
  • Suction Temperature (T suction): The suction temperature of the refrigeration system in degrees Fahrenheit, useful for determining refrigerant superheat.
  • Suction Pressure (P suction): The suction pressure of the refrigeration system in psig.
  • Percent Savings (% SVGS): Displays the compressor operating time versus the dryer's total operational time.
  • Cumulative Dryer Hours (CUM DRYER HR): The total operational time of the dryer in hours.
  • Cumulative Compressor Operating Hours (CUM CMP HR): The total energized time of the refrigeration compressor in hours.

The dryer supports three start modes:

  • Manual Mode: The dryer ships in this mode. After power is supplied and the anti-short cycle (ASC) delay times out, the dryer starts only when the ON button is pressed. To restart, the ON button must be manually depressed.
  • Auto Restart Mode: After power is applied and the ASC delay times out, the dryer starts automatically. Manual control via ON & OFF pushbuttons is still possible. This mode is useful for automatic restarting after power failures.
  • Remote Automatic Mode: Allows remote control of the dryer via a customer-supplied contact. The dryer starts automatically once the switch is closed and the ASC delay times out. Manual control via ON & OFF pushbuttons is still possible. The remote alarm contact signal must be 24V.

Maintenance Features

Regular maintenance is crucial for optimal performance and longevity.

  • Condensate Discharge System: The service unit should be replaced annually. Before maintenance, ensure the system is depressurized. The service unit can be removed by pressing a latching hook, detaching the Bekomat from the outlet, removing the design shell, and pulling the service unit from the pipe.
  • Refrigerant Condenser: For standard dryers, regular inspection and cleaning of the condenser is recommended. Ingersoll Rand dryers may be equipped with an optional ambient air filter designed to protect the condenser from dirt and debris. If present, this filter should be inspected and cleaned regularly. Annual replacement of the filter is recommended, or more frequent inspection and cleaning may be required depending on the application.
  • Prefilters and Afterfilters: Filter elements should be changed every 6 to 12 months. Carbon elements should be changed when hydrocarbons are first detected downstream or every six months, whichever comes first. When replacing filter elements, all elements should be replaced simultaneously to avoid reduced air quality. Before disassembling filters, depressurize the system to prevent injury or death.
  • Automatic Drains: Isolate the air (gas) supply and depressurize the drain by opening the vent valve before removal. The drain can then be dismantled by removing the clamp ring. When replacing the drain, do not pressurize the unit until the drain bowl is in position and the clamp ring is locked.
  • Technician Mode: This protected mode allows qualified service personnel to manipulate several parameters not accessible to the typical operator and to view factory settings for troubleshooting. To enter, press the "2" and "3" buttons simultaneously. Parameters like "NO-LOSS DRAIN VALVE ENABLE" and "CRANKCASE HEATER DELAY" can be adjusted. Altering these settings without proper instruction from Ingersoll Rand Service Personnel can damage the dryer.

Safety Precautions

  • Always read all instructions completely before operating the unit.
  • Only qualified personnel should adjust, perform maintenance, or repair the dryer.
  • Pull the main electrical disconnect switch and any separate control lines before working on the unit.
  • Do not service any part while the machine is operational.
  • Relieve the entire air system of pressure before removing any parts.
  • Remove and contain refrigerant in accordance with EPA and local regulations before working on the refrigeration system.
  • Do not operate the dryer at pressures exceeding its rating.
  • Do not operate the dryer without guards, shields, and screens in place.
  • Inspect the unit daily for unsafe operating conditions.
  • Never attempt to lift heavy objects without proper lifting equipment.
  • Ensure all customer electrical connections are made at the designated location and follow all NEC, state, local, and other applicable codes.
  • Removing fuses does not disconnect power from the dryer; always disconnect power from all sources before performing service.
  • The fan may start automatically at any time.
  • The unit is charged with refrigerant under high pressure.
  • High voltage is present in the electrical connection box. Turn off power and lock out all sources before opening for service.
  • The remote alarm contact wiring has control power from a separate source.
  • Air under pressure can cause injury, death, or property damage. Do not exceed pressure rating, relieve pressure before servicing, and do not modify/repair/rework ASME coded pressure vessels.
  • Condensate drain discharges under pressure and requires periodic cleaning.
  • Failure to comply with instructions may void the warranty.
  • Always use a backup wrench when making threaded connections to the dryer to prevent damage to tubing and internal components.
  • The dryer should not be located in areas where ambient temperatures are likely to exceed 113°F (45°C) or be less than 50°F (10°C).
  • Ensure sufficient clearance (minimum 18 inches) from walls and other equipment for servicing and maintenance.
  • If installed after reciprocating compressors, add proper vibration isolation and pulsation dampening devices.
  • A pre-filter is recommended to protect the dryer from contamination and ensure maximum performance.

Ingersoll-Rand 1200 Specifications

General IconGeneral
BrandIngersoll-Rand
Model1200
CategoryDryer
LanguageEnglish

Related product manuals