Configuration manual
System Parameters 11
Chapter 3
System Parameters
The configuration of the Previdia Compact control panel, its interfaces and external connections provides for the settings
of a series of parameters reachable from the control panel by accessing control panel programming (paragraph 2.2) and
then pressing the Configuration button on the menu shown on the screen.
Once inside the Configuration menu (paragraph 2.3), the control panel screen will show an image of the control panel
front plate highlighting the access buttons to the configuration sections.
3.1 General parameters of the control panel
Tapping on the appropriate icon inside the control panel configuration screen accesses the configuration
section of some of the control panel parameters.
The available parameters are:
• Panel name, editable field for the description of the
control panel
• Mains failure delay, field for the delay (expressed in
minutes) which must pass between detection of mains
failure by the control panel and mains failure signalling
• Disable buzzer, option that, if activated, disables the
control panel buzzer
• Direct alarm on second pre-alarm, option that, if
activated, generates an alarm signal as soon as two
detectors go into pre-alarm status, regardless of the zone
they belong to. Otherwise the alarm condition will
activate at the end of the first pre-alarm time.
The Esc and Set buttons will allow you to exit the section
without changing the programming or saving it.
3.2 Configuration of the Inim Cloud fire service
Tapping on the appropriate icon inside the control panel configuration screen accesses the configuration
section of the Inim Cloud service.
A window will open containing the following buttons:
• Parameter, for the modification of some parameters related to the Cloud
• Enroll, for the registration procedure of the control panel to the installer account (refer to paragraph 3.2.1 Registration
of the control panel to Inim Cloud)
• Net diagnostics to start a procedure to check the various network functions required to communicate with the Cloud
and obtain useful information in the event of problems.
The information obtained is displayed in the box to the left of the section that opens.
Previdia Compact Panel name
060 Mains failure delay (min)
Disable buzzer
Esc
Direct alarm on second pre-alarm
Set
Access level:3