- 13 -
3 Wiring
H2U-232-CAB (Order No.: 15042148)
Cable connector and
pin
5
1
9 6
DB9 female
8-pin DIN round port
Signal level
RS232, wiht built in RS232
-RS422 transfer circuit
RS422
Internal connection
between the cables
Pin No. Signal Pin No. Signal
1 4 TX-
2 RXD 7 TX+
3 TXD 1 RX-
4 2 RX+
5 GND 3 GND
Model and port using
the cable
IT5*** HMI COM2[RS232]
IT6***E HMI COM2[RS232]
Inovance H1U/H2U/H3U
RS422 communication port
Mitsubishi FX1N/2N/3U/3G
RS422 communication port
HMI user program
setting when using this
cable
Set COM2 to RS232.
Select the same communication protocol and data
format for the HMI and the PLC.
3.2.4 Precautions on Communication Connection
Cable requirements: Use different cables for connection of different external
devices. Do not lay the communication cable together with the AC power cables
or near sources of electrical noise. Do not plug/remove the communication cable
during communication.
To avoid communication problems, ensure:
Communication cable ≤ 150 m when connecting RS485/422 devices
Communication cable ≤ 15 m when connecting RS232 devices
If a communication problem exists, “Out time” will display on the screen and
disappears only after the communication becomes normal.
Use a shielded cable as the communication cable if the cable is too long or needs to
run through the electrical noise environment.