6 Troubleshooting
6. Troubleshooting
If the HMI touch screen becomes insensitive or abnormal, use the touch calibration
program to calibrate it.
Step 1:
When powering on the HMI, hold down the screen to enter "Login" interface (the
system automatically enters calibration program if the Password box is not touched
within 20s) .Input the default password 111111 and the "Setting" menu will appear.
And then press "Touch".