MD021 Plastic Wire Drawing Machine User Manual
5
Wire-break
fault input
Wire-break fault signals can be input
by means of the DIs, so that the
inverter can implement fault
monitoring on external devices. If
the DI receives a fault signal, the
inverter stops and reports Err17.
Note: When "Frequency source selection" (F0-01) is set to 1 (Special
wrap-up mode for wire drawing machine) and "Command source
selection" (F0-00) is set to 1 (Terminal input), the current terminal that
is on can be set to off to reset the inverter after a fault occurs during
running.
Function Code
Name
Range
Default
F1-02
DI filter time
1s to 10s
4s
If misoperation may occur due to interference to the DIs, increase the
value of this parameter to increase the anti-interference capability.
This, however, reduces sensitivity of the DIs.
Function
Code
Name
Range
Default
F1-03
AI minimum input
0.00 V to
5.00 V
0.00 V
F1-04
Corresponding
-100.0% to
0.0%