MD380 User Manual Function Code Table
- 101 -
Function
Code
Parameter Name
Setting Range
Default Property
F8-48 Cooling fan control
0: Fan working during running
1: Fan working continuously
0 ☆
F8-49 Wakeup frequency
Dormant frequency (F8-51) to
maximum frequency (F0-10)
0.00 Hz ☆
F8-50 Wakeup delay time
0.0–6500.0s
0.0s ☆
F8-51 Dormant frequency
0.00 Hz to wakeup frequency (F8-
49)
0.00 Hz ☆
F8-52 Dormant delay time
0.0–6500.0s
0.0s ☆
F8-53
Current running time
reached
0.0–6500.0 min
0.0 min ☆
F8-54
Output power correction
coefcient
0.00%–200 .0%
100.0% ☆
Group F9: Fault and Protection
F9-00
Motor overload protection
selection
0: Disabled
1: Enabled
1 ☆
F9-01
Motor overload protection
gain
0.20–10.00
1.00 ☆
F9-02
Motor overload warning
coefcient
50%–100%
80% ☆
F9-03 Overvoltage stall gain
0 (no stall overvoltage)–100
0 ☆
F9-04
Overvoltage stall protective
voltage
120%–150%
130% ☆
F9-05 Overcurrent stall gain
0–100
20 ☆
F9-06
Overcurrent stall protective
current
100%–200%
150% ☆
F9-07
Short-circuit to ground upon
power-on
0: Disabled
1: Enabled
1 ☆
F9-09 Fault auto reset times
0–20
0 ☆
F9-10
DO action during fault auto
reset
0: Not act
1: Act
0 ☆
F9-11
Time interval of fault auto
reset
0.1s–100.0s
1.0s ☆
F9-12
Input phase loss protection/
contactor energizing
protection selection
Unit's digit: Input phase loss
protection
Ten's digit: Contactor energizing
protection
0: Disabled
1: Enabled
11 ☆
F9-13
Output phase loss protection
selection
0: Disabled
1: Enabled
1 ☆