Function Code Table
MD380 User Manual
- 106 -
Function
Code
Parameter Name
Setting Range
Default Property
F9-55
Backup frequency upon
abnormality
0.0%–100.0% (maximum
frequency)
100.0% ☆
F9-56
Type of motor temperature
sensor
0: No temperature sensor
1: PT100
2: PT1000
1 ☆
F9-57
Motor overheat protection
threshold
0–200°C
110
°C
☆
F9-58
Motor overheat warning
threshold
0–200°C
90
°C
☆
F9-59
Action selection at
instantaneous power failure
0: Invalid
1: Decelerate
2: Decelerate to stop
0 ☆
F9-60
Action pause judging voltage
at instantaneous power
failure
80.0%–100.0%
90.0% ☆
F9-61
Voltage rally judging time at
instantaneous power failure
0.00–100.00s
0.50s ☆
F9-62
Action judging voltage at
instantaneous power failure
60.0%–100.0% (standard bus
voltage)
80.0% ☆
F9-63
Protection upon load
becoming 0
0: Disabled
1: Enabled
0 ☆
F9-64
Detection level of load
becoming 0
0.0%–100.0% (rated motor
current)
10.0% ☆
F9-65
Detection time of load
becoming 0
0.0–60.0s
1.0s ☆
F9-67 Over-speed detection value
0.0%–50.0% (maximum
frequency)
20.0% ☆
F9-68 Over-speed detection time
0.0–60.0s
1.0s ☆
F9-69
Detection value of too large
speed deviation
0.0%–50.0% (maximum
frequency)
20.0% ☆
F9-70
Detection time of too large
speed deviation
0.0–60.0s
5.0s ☆
Group FA: Process Control PID Function
FA-00 PID setting source
0: FA-01
1: AI1
2: AI2
3: AI3
4: Pulse setting (DI5)
5: Communication setting
6: Multi-reference
0 ☆
FA-01 PID digital setting
0.0%–100.0%
50.0% ☆