MD380 User Manual Function Code Table
- 113 -
Function
Code
Parameter Name
Setting Range
Default Property
FD-03 Response delay
0–20 ms
Valid for Modbus
2 ms ☆
FD-04 Communication timeout
0.0s (invalid)
0.1–60.0s
Valid for Modbus, PROFIBUS-DP
and CANopen
0.0s ☆
FD-05
Modbus protocol selection
and PROFIBUS-DP data
format
Unit's digit: Modbus protocol
30 ☆
0: Non-standard Modbus protocol
1: Standard Modbus protocol
Ten's digit: PROFIBUS-DP data
format
0: PPO1 format
1: PPO2 format
2: PPO3 format
3: PPO5 format
FD-06
Communication reading
current resolution
0: 0.01A
1: 0.1A
0 ☆
FD-08
CANlink communication
timeout time
0.0s: Invalid
0.1–60.0s
0 ☆
Group FE: User-dened Parameters
FE-00
User-dened function code 0
F0-00 to FP-xx
A0-00 to Ax-xx
U0-xx to U0-xx
F0-10 ☆
FE-01
User-dened function code 1
F0-02 ☆
FE-02
User-dened function code 2
F0-03 ☆
FE-03
User-dened function code 3
F0-07 ☆
FE-04
User-dened function code 4
F0-08 ☆
FE-05
User-dened function code 5
F0-17 ☆
FE-06
User-dened function code 6
F0-18 ☆
FE-07
User-dened function code 7
F3-00 ☆
FE-08
User-dened function code 8
F3-01 ☆
FE-09
User-dened function code 9
F4-00 ☆
FE-10
User-dened function code 10
F4-01 ☆
FE-11
User-dened function code 11
F4-02 ☆
FE-12
User-dened function code 12
F5-04 ☆
FE-13
User-dened function code 13
F5-07 ☆
FE-14
User-dened function code 14
F6-00 ☆