MD380 User Manual Function Code Table
- 123 -
Function
Code
Parameter Name
Setting Range
Default Property
A3-34
Number of pole pairs of
resolver
1–65535
1 ★
A3-36
Encoder wire-break fault
detection time
0.0s: No action
0.1–10.0s
0.0s ★
A3-37 Auto-tuning selection
0: No auto-tuning
1: Asynchronous motor static
auto-tuning
2: Asynchronous motor complete
auto-tuning
11: Synchronous motor with-load
auto-tuning
12: Synchronous motor no-load
auto-tuning
0 ★
A3-38
Speed loop proportional gain 1
0–100
30 ☆
A3-39 Speed loop integral time 1
0.01–10.00s
0.50s ☆
A3-40 Switchover frequency 1
0.00 to A2-43
5.00 Hz ☆
A3-41
Speed loop proportional gain 2
0–100
15 ☆
A3-42 Speed loop integral time 2
0.01–10.00s
1.00s ☆
A3-43 Switchover frequency 2
A2-40 to maximum output
frequency
10.00 Hz ☆
A3-44 Vector control slip gain
50%–200%
100% ☆
A3-45
Time constant of speed loop
lter
0.000–0.100s
0.000s ☆
A3-46
Vector control over-
excitation gain
0–200
64 ☆
A3-47
Torque upper limit source in
speed control mode
0: A2-48
1: AI1
2: AI2
3: AI3
4: Pulse setting (DI5)
5: Via communication
6: MIN (AI1,AI2)
7: MAX (AI1,AI2)
0 ☆
A3-48
Digital setting of torque
upper limit in speed control
mode
0.0%–200.0%
150.0% ☆
A3-51
Excitation adjustment
proportional gain
0–20000
2000 ☆
A3-52
Excitation adjustment
integral gain
0–20000
1300 ☆