EasyManua.ls Logo

Inovance MD380S2.2GB - Page 142

Inovance MD380S2.2GB
304 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Description of Function Codes
MD380 User Manual
- 142 -
 0: Digital setting (non-retentive at power down)
The initial value of the frequency reference is the value of F0-08 (Preset frequency).
You can change the frequency reference by pressing and on the operation
SDQHORUXVLQJWKH83'2:1IXQFWLRQRILQSXWWHUPLQDOV
:KHQWKH$&GULYHLVSRZHUHGRQDJDLQDIWHUSRZHUGRZQWKHIUHTXHQF\UHIHUHQFH
restores to the value of F0-08.
 1: Digital setting (retentive at power down)
The initial value of the frequency reference is the value of F0-08 (Preset frequency).
You can change the frequency reference by pressing keys
and on the
RSHUDWLRQSDQHORUXVLQJWKH83'2:1IXQFWLRQRILQSXWWHUPLQDOV
:KHQWKH$&GULYHLVSRZHUHGRQDJDLQDIWHUSRZHUGRZQWKHIUHTXHQF\UHIHUHQFHLV
the value memorized at the moment of the last power down.
Note that F0-23 (Retentive of digital setting frequency upon stop) determines whether
the frequency reference is memorized or cleared when the AC drive stops. It is related
to stop rather than power down.
 2: AI1
 3: AI2
 4: AI3
The frequency reference is set by analog input. The MD380 control board provides two
$,WHUPLQDOV$,$,$QRWKHU$,WHUPLQDO$,LVSURYLGHGE\WKH,2H[WHQVLRQFDUG
AI1 is 0–10 V voltage input, AI2 is 0–10 V voltage input or 0–20 mA current input,
determined by jumper J8, and AI3 is 0–10 V voltage input.
7KH0'SURYLGHV¿YHFXUYHVLQGLFDWLQJWKHPDSSLQJUHODWLRQVKLSEHWZHHQWKHLQSXW
voltage of AI1, AI2 and AI3 and the frequency reference, three of which are linear
(point-point) correspondence and two of which are four-point correspondence curves.
You can set the curves by using function codes F4-13 to F4-27 and function codes in
group A6, and select curves for AI1, AI2 and AI3 in F4-33.
:KHQ$,LVXVHGDVWKHIUHTXHQF\VHWWLQJVRXUFHWKHFRUUHVSRQGLQJYDOXHRIWKH
voltage/current input corresponds to the value of F0-10 (Maximum frequency).
 5: Pulse reference (DI5)
The frequency reference is input by means of DI5 (high-speed pulse). The signal
VSHFL¿FDWLRQRISXOVHUHIHUHQFHLV±9YROWDJHUDQJHDQG±N+]IUHTXHQF\
range).
You can set the mapping relationship between DI5 pulse reference and the
corresponding setting in F4-28 to F4-31, and the relationship is a linear curve. 100%
of the corresponding setting of pulse reference corresponds to the value of F0-10
(Maximum frequency).