MD380 User Manual Function Code Table
- 115 -
Function
Code
Parameter Name
Setting Range
Default Property
Group FA: PID Function
FA-00 PID reference source
0: FA-01
1: AI1
2: AI2
3: AI3
4: Pulse reference (DI5)
5: Communication reference
6: Multi-reference
0 ƿ
FA-01 PID digital setting
0.0%–100.0%
50.0% ƿ
FA-02 PID feedback source
0: AI1
1: AI2
2: AI3
3: AI1-AI2
4: Pulse reference (DI5)
5: Communication reference
6: AI1 + AI2
7: MAX (|AI1|, |AI2|)
8: MIN (|AI1|, |AI2|)
0 ƿ
FA-03 PID action direction
0: Forward action
1: Reverse action
0 ƿ
FA-04
PID reference feedback
range
0–65535
1000 ƿ
FA-05 Proportional gain Kp1
0.0–100.0
20.0 ƿ
FA-06 Integral time Ti1
0.01–10.00s
2.00s ƿ
FA-07 Differential time Td1
0.00–10.000
0.000s ƿ
FA-08
Cut-off frequency of PID
reverse rotation
0.00 to maximum frequency
2.00 Hz ƿ
FA-09 PID deviation limit
0.0%–100.0%
0.0% ƿ
FA-10 PID differential limit
0.00%–100.00%
0.10% ƿ
FA-11 PID reference change time
0.00–650.00s
0.00s ƿ
FA-12 3,'IHHGEDFN¿OWHUWLPH
0.00–60.00s
0.00s ƿ
FA-13 3,'RXWSXW¿OWHUWLPH
0.00–60.00s
0.00s ƿ
FA-14 Reserved
-
- ƿ
FA-15 Proportional gain Kp2
0.0–100.0
20.0 ƿ
FA-16 Integral time Ti2
0.01–10.00s
2.00s ƿ
FA-17 Differential time Td2
0.000–10.000s
0.000s ƿ