EasyManua.ls Logo

Inovance MD380T2.2GB - Page 116

Inovance MD380T2.2GB
304 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Function Code Table
MD380 User Manual
- 116 -
Function
Code
Parameter Name
Setting Range
Default Property
FA-18
PID parameter switchover
condition
0: No switchover
1: Switchover via DI
2: Automatic switchover based on
deviation
3: Automatic switchover based on
running frequency
0 ƿ
FA-19
PID parameter switchover
deviation 1
0.0% to FA-20
20.0% ƿ
FA-20
PID parameter switchover
deviation 2
FA-19 to 100.0%
80.0% ƿ
FA-21 PID initial value
0.0%–100.0%
0.0% ƿ
FA-22 PID initial value active time
0.00–650.00s
0.00s ƿ
FA-23
Maximum deviation between
two PID outputs in forward
direction
0.00%–100.00%
1.00% ƿ
FA-24
Maximum deviation between
two PID outputs in reverse
direction
0.00%–100.00%
1.00% ƿ
FA-25 PID integral property
8QLWVGLJLW,QWHJUDOVHSDUDWHG
00 ƿ
0: Invalid
1: Valid
7HQVGLJLW:KHWKHUWRVWRS
integral operation when the output
reaches the limit)
0: Continue integral operation
1: Stop integral operation
FA-26
Detection level of
PID feedback loss
0.0%: No detection
0.1%–100.0%
0.0% ƿ
FA-27
Detection time of
PID feedback loss
0.0–20.0s
0.0s ƿ
FA-28 PID operation at stop
0: Disabled
1: Enabled
0 ƿ