Function Code Table
MD380 User Manual
- 116 -
Function
Code
Parameter Name
Setting Range
Default Property
FA-18
PID parameter switchover
condition
0: No switchover
1: Switchover via DI
2: Automatic switchover based on
deviation
3: Automatic switchover based on
running frequency
0 ƿ
FA-19
PID parameter switchover
deviation 1
0.0% to FA-20
20.0% ƿ
FA-20
PID parameter switchover
deviation 2
FA-19 to 100.0%
80.0% ƿ
FA-21 PID initial value
0.0%–100.0%
0.0% ƿ
FA-22 PID initial value active time
0.00–650.00s
0.00s ƿ
FA-23
Maximum deviation between
two PID outputs in forward
direction
0.00%–100.00%
1.00% ƿ
FA-24
Maximum deviation between
two PID outputs in reverse
direction
0.00%–100.00%
1.00% ƿ
FA-25 PID integral property
8QLWVGLJLW,QWHJUDOVHSDUDWHG
00 ƿ
0: Invalid
1: Valid
7HQVGLJLW:KHWKHUWRVWRS
integral operation when the output
reaches the limit)
0: Continue integral operation
1: Stop integral operation
FA-26
Detection level of
PID feedback loss
0.0%: No detection
0.1%–100.0%
0.0% ƿ
FA-27
Detection time of
PID feedback loss
0.0–20.0s
0.0s ƿ
FA-28 PID operation at stop
0: Disabled
1: Enabled
0 ƿ