Function Code Table
- 122 -
Function
Code
Parameter Name
Setting Range
Default Property
A3-08
Leakage inductive reactance
(asynchronous motor)
0.01–655.35 mH (AC drive power
≤ 55 kW)
0.001–65.535 mH (AC drive
power > 55 kW)
Model
dependent
★
A3-09
Mutual inductive reactance
(asynchronous motor)
0.1–6553.5 mH (AC drive power
≤ 55 kW)
0.01–655.35 mH (AC drive power
> 55 kW)
Model
dependent
★
A3-10
No-load current
(asynchronous motor)
0.01 A to A2-03 (AC drive power
≤ 55 kW)
0.1 A to A2-03 (AC drive power >
55 kW)
Model
dependent
★
A3-16
Stator resistance
(synchronous motor)
0.001–65.535 Ω (AC drive power
≤ 55 kW)
0.0001–6.5535 Ω (AC drive
power > 55 kW)
Model
dependent
★
A3-17
Shaft D inductance
(synchronous motor)
0.01–655.35 mH (AC drive power
≤ 55 kW)
0.001–65.535 mH (AC drive
power > 55 kW)
Model
dependent
★
A3-18
Shaft Q inductance
(synchronous motor)
0.01–655.35 mH (AC drive power
≤ 55 kW)
0.001–65.535 mH (AC drive
power > 55 kW)
Model
dependent
★
A3-20
Back EMF (synchronous
motor)
0.1–6553.5 V
Model
dependent
★
A3-27
Encoder pulses per
revolution
1–65535
1024 ★
A3-28 Encoder type
0: ABZ incremental encoder
1: UVW incremental encoder
2: Resolver
3: SIN/COS encoder
4: Wire-saving UVW encoder
0 ★
A3-30
A, B phase sequence of ABZ
incremental encoder
0: Forward
1: Reserve
0 ★
A3-31 Encoder installation angle
0.0°–359.9°
0.0° ★
A3-32
U, V, W phase sequence of
UVW encoder
0: Forward
1: Reverse
0 ★
A3-33
UVW encoder angle offset 0.0°–359.9° 0.0°
★