Options
‑58‑
Structure Model
RST/UVW
Grounding Wire
Screw
Recommend
ed Cable
(mm
2
)
<1>
Recommend
ed Cable Lug
Recommend
ed Cable
(mm
2
)
<1>
Recommend
ed Cable Lug
T10
MD520‑2T90(S) 2 x (3 x 120)
BC120‑12 120 BC120‑12 M12
MD520‑2T110(S) 2 x (3 x 150)
BC150‑12 150 BC150‑12 M12
T11
MD520‑2T132(S) 2 x (3 x 185)
BC185‑16 185 BC185‑16 M16
T12
MD520‑2T160(S) 2 x (3 x 240)
BC240‑16 240 BC240‑16 M16
MD520‑2T200(S) 2 x (3 x 240)
BC240‑16 240 BC240‑16 M16
Table 5–6 Cable selection (single phase 200‑240 V)
Structure Model
RST/UVW
Grounding Wire
Screw
Recommend
ed Cable
(mm
2
)
<1>
Recommend
ed Cable Lug
Recommend
ed Cable
(mm
2
)
<1>
Recommend
ed Cable Lug
T2
MD520‑2S0.4B(S)
0.75 TNR0.75‑4 0.75 TNR8‑5
M4
MD520‑2S0.7B(S)
1.5 TNR0.75‑4 1.5 TNR8‑5
MD520‑2S1.5B(S)
2.5 TNR1.25‑4 1.5 TNR8‑5
MD520‑2S2.2B(S)
4 TNR2‑4 2.5 TNR8‑5
Table 5–7 Cable selection (single phase 200–240 V) (with UL certification)
Structure Model
RST/UVW
Grounding Wire
Screw
Recommended
Cable (AWG)
Cable Lug
Model
Recommended
Cable (AWG)
Cable Lug
Model
T2
MD520‑2S0.4B(S)
14 TLK2.5‑4 2 x 14 TLK2.5‑4
M4
MD520‑2S0.7B(S)
14 TLK2.5‑4 2 x 14 TLK2.5‑4
MD520‑2S1.5B(S)
14 TLK2.5‑4 2 x 14 TLK2.5‑4
MD520‑2S2.2B(S)
10 TLK6‑4 2 x 10 TLK6‑4
<1>: Chinese standards applicable; 3 x 10: one three‑conductor cable; 2 x (3 x 95): two
three‑conductor cables; <2>: American standards applicable; 5: 5AWG; 1/0: 0AWG; 2/0:
00AWG; 3/0: 000AWG; 4/0: 0000AWG; and 2 x 250: two 250 kcmil cables.
Recommended lug
The recommended lugs are the TNR, GTNR, and BC series lugs of Suzhou Yuanli. The
lugs with UL certifications are KST's TLK and SQNBS series lugs.