Options
‑64‑
Table 5–12 Selection of fuses, contactors, and circuit breakers (three phase 200‑240 V)
Structure Model
Fuse
Bussmann
Contactor Circuit Breaker
Rated Current (A)
Model
Rated Current (A) Rated Current (A)
T1
MD520‑2T0.4B(S)
10 FWP‑10B 9 6
MD520‑2T0.7B(S)
10 FWP‑10B 9 10
MD520‑2T1.1B(S)
15 FWP‑15B 12 13
MD520‑2T1.5B(S)
20 FWP‑20B 16 16
T2
MD520‑2T2.2B(S)
30 FWP‑30B 26 25
MD520‑2T3.7B(S)
40 FWP‑40B 26 32
T3
MD520‑2T5.5B(S)
70 FWP‑70B 50 63
T4
MD520‑2T7.5B(S)
70 FWH‑70B 50 63
T5
MD520‑2T11(B)(S)
125 FWH‑125B 80 80
T6
MD520‑2T15(B)(S)
125 FWH‑125B 80 100
MD520‑2T18.5(B)(S)
150 FWH‑150B 95 160
T7
MD520‑2T22(B)(S)
200 FWH‑200B 115 160
MD520‑2T30(B)(S)
250 FWH‑250A 150 250
T8
MD520‑2T37(B)(S)
275 FWH‑275A 170 250
MD520‑2T45(S)
325 FWH‑325A 205 250
MD520‑2T55(S)
400 FWH‑400A 245 400
T9
MD520‑2T75(S)
600 FWH‑600A 410 500
T10
MD520‑2T90(S)
600 FWH‑600A 410 500
MD520‑2T110(S)
700 FWH‑700A 410 630
T11
MD520‑2T132(S)
800 FWH‑800A 475 630
T12
MD520‑2T160(S)
1000 170M5016 620 800
MD520‑2T200(S)
1400 170M6017 800 1000
Table 5–13 Selection of fuses, contactors, and circuit breakers (single phase 200‑240 V)
Structure Model
Fuse
Bussmann
Contactor Circuit Breaker
Rated Current (A)
Model
Rated Current (A) Rated Current (A)
T2
MD520‑2S0.4B(S)
10 FWP‑10B 9 10
MD520‑2S0.7B(S)
15 FWP‑15B 12 13
MD520‑2S1.5B(S)
20 FWP‑20B 16 16
MD520‑2S2.2B(S)
30 FWP‑30B 30 32
Note
See "Requirements on Protective Devices" in section “UL/cUL Certification" for require‑
ments on fuses and circuit breakers of UL‑compliant drives.