Chapter 5 Function Code Table
The symbols in the function code table are described as follows:
"": The parameter can be modified when the drive is in either stop or running state.
"": The parameter cannot be modified when the drive is in the running state.
"●": The parameter is the actually measured value and cannot be modified.
Function
Code
Parameter
Name
Setting
Range
Parameter
Description
Min.
Unit
Default
Property
Group F0
P0-00
Braking
start
voltage
Voltage class:
1) 220 V: P0-01
to 390.0 V
2) 380 V: P0-01
to 730.0 V
3) 480 V: P0-01
to 820.0 V
The braking unit
starts braking
when the bus
voltage is higher
than the value.
0.1 V
Voltage
class:
1) 220 V:
350.0 V
2) 380 V:
670.0 V
3) 480 V:
760.0 V
P0-01
Braking
stop
voltage
Voltage class:
1) 220 V: 320 V
to P0-00
2) 380 V: 620 V
to P0-00
3) 480 V: 700 V
to P0-00
The braking unit
stops braking
when the bus
voltage is lower
than the value.
0.1 V
Voltage
class:
1) 220 V:
340.0 V
2) 380 V:
650.0 V
3) 480 V:
730.0 V
P0-02
Start
braking
rate
1%100%
This parameter
specifies the
duty ratio when
the bus voltage
is equal to the
value of P0-00.
1%
100
P0-03
Master/Sla
ve mode
selection
0: Master
1: Slave
This parameter
specifies
whether the
working mode of
the braking unit
is master or
slave.
1
0
P0-04
Reserved
-
-
-
-
-
P0-05
Reserved
-
-
-
-
-
P0-06
Restore
default
setting
0: Not restore
1: Only restore
group P0
2: Clear all
information of
group P2
-
1
0