User Guide
A01
Data code 19010735
NICE3000
new
Series Integrated Elevator Controller Advanced User Guide
Copyright   Shenzhen Inovance Technology Co., Ltd.
Integrated Elevator Controller
Advanced User Guide
NICE3000
new
Series

Table of Contents

Other manuals for Inovance Monarch NICE-L-C-4045

Questions and Answers

  • M
    Melody ThomasNov 22, 2025
    How to troubleshoot overcurrent during acceleration with Inovance Controller?
    • S
      Shawn RichardNov 22, 2025
      If you are experiencing overcurrent during acceleration with your Inovance Controller, there are several potential causes to investigate. First, the main circuit output might be grounded or short-circuited, so check the motor cables and PE cable for incorrect connections, verify that a shorting PMSM stator contactor isn't causing a short circuit at the controller output side, and inspect the motor cables for damaged jackets. Second, improper motor auto-tuning can lead to this issue, so set the motor parameters correctly according to the motor nameplate and perform motor auto-tuning again. Finally, an incorrect encoder signal can also cause overcurrent, so check whether encoder pulses per revolution (PPR) is set correctly, ensure the encoder signal isn't being interfered with, verify the en...
  • A
    alexnelsonSep 4, 2025
    What should I do if my Inovance Monarch NICE-L-C-4045 reports a power supply phase loss?
    • M
      Michael MurraySep 4, 2025
      If your Inovance Controller reports a power supply phase loss, it indicates that the power input phases are not symmetric. First, check whether any phase of the three-phase power supply is lost. Then, verify whether the three phases of the power supply are balanced. Also, check whether the power voltage is normal, and adjust the power voltage if necessary. For 220 V models, you can set FC-01 bit 14 to 1 to cancel detection of this fault.
  • D
    Derek YoungSep 7, 2025
    What are the common causes of motor auto-tuning faults in Inovance Monarch NICE-L-C-4045 Controller?
    • H
      hwilliamsonSep 7, 2025
      A motor auto-tuning fault in your Inovance Controller can occur for various reasons: * If learning the stator resistance fails, check whether the motor wiring is correct. * If learning the magnetic pole position fails. * If the synchronous motor static auto-tuning mode is selected, but the encoder is not SIN/COS, select another auto-tuning mode or use a SIN/ COS encoder. * If CD signal fluctuation is large in synchronous motor static auto-tuning, hardware interference exists. Check whether grounding is correct. * If Leaning the encoder zero- position angle fails in synchronous motor angle-free auto- tuning, obtain the encoder zero-point angle in inspection state, and then perform half- automatic angle-free auto-tuning under normal-speed running.
  • M
    Michelle MillerSep 8, 2025
    What should I check if my Inovance Monarch NICE-L-C-4045 indicates a power output phase loss?
    • S
      Sarah PhamSep 8, 2025
      If your Inovance Controller indicates a power output phase loss, the issue likely stems from the output wiring of the main circuit being loose. Check whether the motor wiring is secure and verify whether the RUN contactor on the output side is normal.
  • M
    Mark NunezSep 10, 2025
    How to troubleshoot a RUN contactor feedback abnormal error on an Inovance Monarch NICE-L-C-4045 Controller?
    • D
      diamondberrySep 10, 2025
      A RUN contactor feedback abnormal error on your Inovance Controller can have a couple of causes: * If the feedback of the RUN contactor is active, but the contactor has no output, check whether the feedback contact of the contactor acts properly and check the signal feature (NO, NC) of the feedback contact. * If the current of the asynchronous motor from acceleration to constant-speed running is too small (? 0.1 A), check whether the output cables UVW of the controller are connected properly and check whether the control circuit of the RUN contactor coil is normal.
  • R
    Ricky CoxSep 12, 2025
    What causes the 'door lock disconnected during running' error in Inovance Monarch NICE-L-C-4045?
    • H
      hollyhillSep 12, 2025
      If your Inovance Controller displays a 'door lock disconnected during running' error, indicated by subcodes 101 or 102, it means the door lock circuit feedback is invalid during elevator operation. Check whether the hall door lock and the car door lock are in good contact. Also, verify whether the door lock contactor acts properly, check the signal feature (NO, NC) of the feedback contact on the door lock contactor, and ensure the external power supply is normal.
  • A
    Amanda ThompsonNov 23, 2025
    What causes overcurrent during deceleration in Inovance Controller and how to fix it?
    • H
      Heidi PageNov 23, 2025
      If your Inovance Controller experiences overcurrent during deceleration, it may be due to a few reasons. A potential cause is that the main circuit output is grounded or short-circuited. To resolve this, check whether the motor cables and PE cable are connected incorrectly, verify that the shorting PMSM stator contactor causes a short circuit at the controller output side, and inspect the motor cables for damaged jacket. Also, improper motor auto-tuning can cause this issue. Ensure you set motor parameters correctly according to the motor nameplate and perform motor auto-tuning again. Another possible cause is an incorrect encoder signal. Verify that encoder pulses per revolution (PPR) is set correctly, check whether the encoder signal is interfered with, ensure the encoder cable runs thro...
  • H
    Heather DelacruzNov 20, 2025
    What to do if my Inovance Monarch NICE-L-C-4045 shows an overload error?
    • M
      millerjosephNov 20, 2025
      If your Inovance Controller is showing an overload error, it could be due to several reasons. First, check if the brake is released and the brake power supply is normal, and also check whether the guide shoes are too tight, since the mechanical resistance may be too large. Then, verify that the balance coefficient is correct. Also, ensure the encoder feedback signal and parameter settings are correct, including the initial angle of the encoder for PMSM. If the elevator running current is higher than normal, check the motor parameter setting and perform motor auto-tuning again. If the issue persists, and this fault is reported when the slip experiment is carried on, perform the slip experiment by using the function set in F3-24. Finally, an incorrect motor phase sequence can cause this, so ...
  • A
    Anthony SmithSep 18, 2025
    What does 'Output abnormal' mean on my Inovance Controller?
    • H
      hansonjenniferSep 18, 2025
      If your Inovance Controller displays 'Output abnormal', it indicates a specific issue: * If the subcode is 1, the braking resistor is short-circuited. Check that wiring of the braking resistor and braking unit is correct, without short circuit and check whether the main contactor works properly and whether there is arch or stuck problem. * If the subcode is 2, the braking IGBT is short-circuited.
  • K
    Kelsey EvansSep 22, 2025
    What to do if Inovance Monarch NICE-L-C-4045 shows overcurrent during acceleration?
    • D
      Daniel HansenSep 22, 2025
      If the Inovance Controller experiences overcurrent during acceleration, several factors could be at play. First, examine the motor and grounding cables to ensure they are correctly connected and that the motor cables do not have damaged jackets. Also, check for short circuits at the controller output side, especially from shorting PMSM stator contactors. Another potential cause is incorrect motor parameters or improper auto-tuning; verify the motor parameters against the nameplate and repeat the motor auto-tuning process. You may also need to reduce the acceleration rate if the acceleration time is too short. Finally, ensure that the phase sequence of the motor is correct by exchanging the motor UVW phase sequence.