Chapter 5: Menu reference
Advisor Advanced ATSx500A(-IP) Installation and Programming Manual 235
8.1.3.5 Final set delay
5 Final set dly
> <
The Final set delay option defines the delay time between the completion of an
area being set by an exit terminator or final door set and the area being armed.
The period allows for devices connected to inputs to return to normal state. The
allowed range is 0 to 255 seconds.
8.1.3.6 Installer in-time
6 Inst in-time
>00:01’00<
The Installer in-time menu allows you to configure the time in which an engineer
is allowed to access when granted by a user (see “8.2.1 User code required” on
page 237). This time starts when the user activates the option “Installer in”.
During this time the installer can enter the installer menu and set or unset the
system.
When the installer is in the installer menu, this time has no effect on how long the
installer can stay logged.
The allowed range is 00 h 01 min to 11 h 59 min. A value of 12 h 00 min is
equivalent to infinite access.
8.1.4 Zone timer menu
1>DblKnock int
10’00
The Zone timer menu allows you to set up all programmable zone timers.
8.1.4.1 Double knock interval
1 DblKnock int
>00’00<
If enabled for a particular zone, Double knock interval specifies the maximum
permitted time between two pulses that will register an alarm. If this value is set
to 0, an alarm condition is not determined by the interval between two pulses, but
determined solely by Double knock open time. The allowed range is 0 to
15 minutes.
8.1.4.2 Double knock open
2 DblKnock open
>00’05<
If enabled for a particular zone, Double knock open specifies the time for which
the zone may remain active. If the zone remains active after this time exceeded,
an alarm is generated without waiting for a second activation.
The input format is mm’ss. The allowed range is from 00’00 to 15’00.

Table of Contents

Other manuals for Interlogix ATS3500A-IP-MM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Interlogix ATS3500A-IP-MM and is the answer not in the manual?

Interlogix ATS3500A-IP-MM Specifications

General IconGeneral
BrandInterlogix
ModelATS3500A-IP-MM
CategorySecurity System
LanguageEnglish

Related product manuals