EasyManua.ls Logo

INVENTOR B2VI-09 - Page 29

INVENTOR B2VI-09
31 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
26
Sheet 2. Additional refrigerant charging amount
for R22 R407C R410A
and R134a
Note: The additional refrigerant charging amount in Sheet 2 is recommended
value, not compulsory.
Diameter of connection pipe mm Indoor unit throttle Outdoor unit throttle
Liquid pipe Gas pipe Cooling only,
cooling and heating
(g / m)
Cooling only
(g / m)
Cooling and
heating (g /
m)
Ф6 Ф9.5 or Ф12 20 15 20
Ф6 or Ф9.5 Ф16 or Ф19 50 15 50
Ф12 Ф19 or Ф22.2 100 30 120
Ф16 Ф25.4 or Ф31.8 170 60 120
Ф19 - 250 250 250
Ф22.2 - 350 350 350
Configuration of connection pipe and additional volume of refrigerant

Other manuals for INVENTOR B2VI-09

Related product manuals