Goodrive20 inverters Function Parameters
81
Function
code
Name Detailed instruction of parameters
Default
value
Modify
during fault 0x00~0x11
LED ones:
0:Action under fault undervoltage
1:No action under fault undervoltage
LED tens:
0:Action during the automatic reset
1:No action during the automatic reset
P11.14
Speed
deviation
detection
0.0~50.0%
Set the speed deviation detection time.
10.0%
P11.15
Speed
deviation
detection time
This parameter is used to set the speed deviation detection
time.
Setting range of P11.15: 0.0~10.0s
0.5s
P11.16
Automatic
frequency-de
creasing at
voltage drop
0:Invalid
1:Valid; ensure rated output torque when voltage drop
0x00
P13 Group Control parameters of SM
P13.13
Braking
current of
short circuit
After the inverter starts, when P01.00=0, set P13.14 to
non-zero value and begin short circuit braking.
After the inverter stops, when the operation frequency is
less than P01.09, set P13.15 to non-zero value and begin
stopping short-circuit braking and then DC braking.
Setting range of P13.13: 0.0~150.0%(inverters)
Setting range of P13.14: 0.00~50.00s
0.0%
P13.14
Braking
retention time
of starting
short circuit
0.00s
P13.15
Braking
retention time
of stopping
short circuit
0.00s
P14 Group Serial communication