Goodrive20 inverters Function Parameters
45
Function
code
Name Detailed instruction of parameters
Default
value
Modify
Torque boost to the output voltage for the features of low
frequency torque. P04.01 is for the Max. output voltage V
b
.
P04.02 defines the percentage of closing frequency of
manual torque to f
b
.
Torque boost should be selected according to the load. The
bigger the load is, the bigger the torque is. Too big torque
boost is inappropriate because the motor will run with over
magnetic, and the current of the inverter will increase to add
the temperature of the inverter and decrease the efficiency.
When the torque boost is set to 0.0%, the inverter is
automatic torque boost.
Torque boost threshold: below this frequency point, the
torque boost is valid, but over this frequency point, the
torque boost is invalid.
The setting range of P04.01:0.0%:(automatic) 0.1%~10.0%
The setting range of P04.02:0.0%~50.0%
0.0% ○
Torque boost
close
20.0% ○
1
When P04.00 =1, the user can set V//F curve through
0.00Hz