Goodrive350 IP55 High-ingress Protection Series VFD Function parameter list
-171-
stator current of the motor increases, while the
rotor current does not change, while the cooling
effect of stator is much more effective than that
of the rotor.
Current
regulation
coefficient on
input side
This function code is used to adjust the current
display value on the AC input side.
0.00–1.00
0: STO alarm lock
Alarm-lock means STO alarm must be reset
after state restoration when STO occurs.
1: STO alarm unlock
Alarm-unlock means when STO occurs, after
state restoration, STO alarm will disappear
automatically.
Bias value of
upper limit
frequency of
torque control
0.00 Hz–P00.03 (max. output frequency)
Acceleration/dec
eleration
selection of
upper limit
frequency of
torque control
0: No limit on acceleration or deceleration
1: Acceleration/deceleration time 1
2: Acceleration/deceleration time 2
3: Acceleration/deceleration time 3
4: Acceleration/deceleration time 4
Enabling auto
carrier frequency
reduction
Temperature
point of auto
carrier frequency
reduction
Interval of carrier
frequency
reduction
AI1
disconnection
detection
threshold
AI2
disconnection
detection
threshold