Goodrive350 IP55 High-ingress Protection Series VFD Function parameter list
-198-
Function
code
Name
Description
Default
value
Modify
address 2
P16.16
Ethernet
monitoring variable
address 3
0x00000xFFFF
0x0000
P16.17
Ethernet
monitoring variable
address 4
0x00000xFFFF
0x0000
P16.18
P16.23
Reserved
P16.24
Identification time
for the expansion
card in card slot 1
0.0600.0s
If it is set to 0.0, identification fault will not be
detected
0.0s
P16.25
Identification time
for the expansion
card in card slot 2
0.0600.0s
If it is set to 0.0, offline fault will not be
detected
0.0s
P16.26
Identification time
for the expansion
card in card slot 3
0.0600.0s
If it is set to 0.0, offline fault will not be
detected
0.0s
P16.27
Communication
timeout period of
expansion card in
card slot 1
0.0600.0s
If it is set to 0.0, offline fault will not be
detected
0.0s
P16.28
Communication
timeout period of
expansion card in
card slot 2
0.0600.0s
If it is set to 0.0, offline fault will not be
detected
0.0s
P16.29
Communication
timeout period of
expansion card in
card slot 3
0.0600.0s
If it is set to 0.0, offline fault will not be
detected
0.0s
P16.30
Reserved
P16.31
PROFINET
communication
timeout time
0.060.0s
5.0s
P16.32
Received PZD2
031
0: Invalid
1: Set frequency (0Fmax. Unit: 0.01Hz)
2: PID reference (-10001000, in which 1000
corresponds to 100.0%)
3: PID feedback (-10001000, in which 1000
corresponds to 100.0%)
4: Torque setting (-3000+3000, in which
1000 corresponds to 100.0% of the motor
rated current)
5: Setting of the upper limit of forward running
0
P16.33
Received PZD3
0
P16.34
Received PZD4
0
P16.35
Received PZD5
0
P16.36
Received PZD6
0
P16.37
Received PZD7
0
P16.38
Received PZD8
0
P16.39
Received PZD9
0