Goodrive350 IP55 High-ingress Protection Series VFD Function parameter list
-234-
Function
code
Name
Description
Default
value
Modify
1: Determined by P00.01
Hundreds: Slave transmitting/master receiving
data enable
0: Enable
1: Disable
P28.03
Slave speed
gain
0.0500.0%
100.0%
P28.04
Slave torque
gain
0.0500.0%
100.0%
P28.05
Master/slave
mode 2 speed
mode / torque
mode switching
frequency point
0.0010.00Hz
5.00Hz
P28.06
Number of
slaves
015
1
P28.07
P28.08
Reserved
/
/
/
P28.09
CAN slave
torque offset
-100.0100.0%
0.0%
P28.10
Enabling
PT100/PT1000
to detect
temperature
0x000x11
Ones place: PT100 temperature detection
0: Disable
1: Enable
Tens place: PT1000 temperature detection
0: Disable
1: Enable
0x00
P28.11
EC PT100
detected OH
protection
threshold
Protection threshold of overheating (OH)
detected by the expansion card (EC) with
PT100.
0.0150.0°C
120.0°C
P28.12
EC PT100
detected OH
pre-alarm
threshold
Pre-alarm threshold of OH detected by the EC
with PT100.
0.0150.0°C
100.0°C
P28.13
EC PT100
detected
temperature
calibration upper
limit
Calibration upper limit of temperature detected
by the EC with PT100.
50.0150.0°C
120.0°C
P28.14
EC PT100
detected
temperature
calibration lower
limit
Calibration lower limit of temperature detected
by the EC with PT100.
-20.050.0°C
10.0°C
P28.15
EC PT100
calibration upper
04096
2950

Table of Contents