Goodrive350 IP55 High-ingress Protection Series VFD Basic Operation Instructions
-72-
Waiting time of DC brake
after stop
Deadzone time of
forward/reverse rotation
Forward/reverse rotation
switch-over mode
0: switch over after zero frequency
1: switch over after starting frequency
2: switch over after passing stop speed
and delay
Stop speed detection mode
0: Set value of speed (the only detection
mode valid in SVPWM mode)
1: Detection value of speed
Power-on terminal running
protection selection
0: Terminal running command is invalid at
power up
1: Terminal running command is valid at
power up
Action selection when the
running frequency is below
lower limit (lower limit should
be larger than 0)
Ones place: Action selection
0: Run at the lower limit frequency
1: Stop
2: Sleep
Tens place: Stop mode
0: Coast to stop
1: Decelerate to stop
0.0–3600.0s (valid when the ones place of
P01.19 is 2)
0: Restart is disabled
1: Restart is enabled
Waiting time of restart after
power cut
0.0–3600.0s (valid when P01.21 is 1)
Open-loop 0Hz output
selection
0: No voltage output
1: With voltage output
2: Output as per DC brake current of stop
Deceleration time of
emergency-stop
Time of starting section of
deceleration S curve