Goodrive350 IP55 High-ingress Protection Series VFD Basic Operation Instructions
-76-
Note: "/" indicates this multi-function terminal is invalid under present reference channel.
When setting the auxiliary frequency inside the VFD via multi-function terminal UP (10) and
DOWN (11), users can increase/decrease the frequency quickly by setting P08.45 (UP
terminal frequency incremental change rate) and P08.46 (DOWN terminal frequency
decremental change rate).
Sx
Sy
UP terminal
function selection=10
DOWN terminal
function selection=11
UP terminal state
DOWN terminal state
T
F
T
T
UP terminal frequency incremental integral speed P08.45
DOWN terminal frequency decremental integral speed P08.46
Related parameter list:
Upper limit of running
frequency
Lower limit of running
frequency
A frequency command
selection
0: Set via keypad
1: Set via AI1
2: Set via AI2
3: Set via AI3
4: Set via high speed pulse HDIA
5: Set via simple PLC program
6: Set via multi-step speed running
7: Set via PID control
8: Set via Modbus/Modbus TCP
communication
9: Set via PROFIBUS/CANopen/
DeviceNet communication
10: Set via Ethernet communication
11: Set via high speed pulse HDIB
12: Set via pulse train AB
13: Set via
EtherCAT/PROFITNET/Ethernet IP
communication
14: Set via PLC card
15: Reserved
B frequency command
selection