Goodrive100-PV Series Solar Pumping VFD Function parameters 
22 
6 Function parameters 
“○”: means the set value of the parameter can be modified on stop and running state; 
“◎”: means the set value of the parameter cannot be modified on the running state; 
“●”: means the value of the parameter is the real detection value which cannot be modified; 
Note:  The  VFD  implements  auto  checking  and  restriction  on  the  parameter  modification 
property. This prevents users from modifying parameters by misoperation. 
6.1 Common function parameters for solar pumping control 
Detailed illustration of parameters 
P00 Group    Basic function group 
0: SVC 0 
No  need  to  install  encoders.  Suitable  in 
applications  which  need  low  frequency, 
big  torque  for  high  accuracy  of  rotating 
speed  and  torque  control.  Relative  to 
mode  1,  it  is  more  suitable  for  the 
applications which need small power. 
1: SVC 1   
1  is  suitable  in  high  performance  cases 
with  the  advantage  of  high  accuracy  of 
rotating  speed  and  torque.  It  does  not 
need to install pulse encoder.   
2: SVPWM control 
2  is suitable in  applications which do  not 
need  high  control  accuracy,  such  as  the 
load of fan and pump, and suitable  when 
one VFD drives multiple motors. 
Note:  In  vector  control,  the  VFD  must 
autotune motor parameters first. 
Select  the  run  command  channel  of  the 
VFD. 
The  control  command  of  the  VFD