Goodrive300-21 Series Dual-inverter
Integrated Machine for Air Compressor

Table of Contents

Questions and Answers

  • M
    Matthew WilsonSep 10, 2025
    What causes pressure alarm in INVT Goodrive300-21 Inverter?
    • R
      Robert GraySep 10, 2025
      The pressure alarm in your INVT Inverter is triggered when the actual pressure detected by P1 is larger than the alarm pressure set by P18.18. Check if solenoid valve is normal and check if pressure control parameters are set correctly.
  • F
    Francis GuzmanAug 23, 2025
    What to do if INVT Goodrive300-21 Inverter shows overvoltage during acceleration?
    • C
      Cynthia PhamAug 23, 2025
      If the INVT Inverter shows overvoltage during acceleration, it could be due to the following reasons: * Check the input power if there is an exception occurred to input voltage. * Check whether load DEC time is too short, or the motor starts during rotating, or additional dynamic brake components is required because of large energy feedback.
  • W
    Wesley HartAug 25, 2025
    Why INVT Inverter shows motor overload?
    • J
      joshuariveraAug 25, 2025
      The INVT Inverter might show a motor overload due to several reasons: * If the grid voltage is too low, check the grid voltage. * If the motor rated current is set incorrectly, reset the motor rated current. * If the motor stall occurs or the load transient is too large, check the load and adjust the torque boost quantity.
  • S
    Suzanne ComptonAug 27, 2025
    What to do if INVT Inverter has RS485 communication fault?
    • J
      Joshua DawsonAug 27, 2025
      If your INVT Inverter is experiencing an RS485 communication fault, consider the following: * Ensure the baud rate is set properly. * Check the wiring of communication interfaces for any faults. * Verify the communication address is set correctly. * If communication suffers from strong interference, replace or change the wiring to enhance the anti-interference capacity.
  • R
    ryan18Aug 28, 2025
    What to do if INVT Inverter shows bus undervoltage fault?
    • S
      Scott KellerAug 28, 2025
      If the INVT Inverter shows a bus undervoltage fault, check the grid input power because the voltage of the grid may be too low.
  • M
    Michele WilliamsAug 29, 2025
    How to troubleshoot phase loss on input side of INVT Inverter?
    • K
      Kristin LewisAug 29, 2025
      To troubleshoot phase loss on the input side of your INVT Inverter: * Check the input power if phase loss or violent fluctuation occurred on input R, S, T. * Check the installation wiring.
  • R
    Rose CooperSep 18, 2025
    What to do for handshake failure on INVT Inverter?
    • D
      Deborah BarreraSep 18, 2025
      If you're experiencing a handshake failure on your INVT Inverter, check whether the handshake between the Plott controller and inverter is performed according to the handshake protocol and check whether P15.10 is set properly, because the handshake process may timeout.
  • E
    elliottbrianSep 12, 2025
    What does temperature alarm mean on INVT Goodrive300-21?
    • C
      Charles WhiteSep 12, 2025
      The temperature alarm in your INVT Inverter is triggered when the actual temperature detected by PT1 is larger than the alarm temperature set by P18.20. Check if control parameters of the fan are set correctly; Check if the fan operates normally; The fan power is too small for effective cooling; Check if there is lubricating oil.
  • O
    ochambersSep 8, 2025
    What does external fault mean on INVT Inverter?
    • M
      manuel93Sep 8, 2025
      An external fault on your INVT Inverter indicates that S external faulty input terminal action. Check external device input.
  • J
    Jill MurphySep 5, 2025
    How to resolve PID feedback offline fault in INVT Inverter?
    • M
      Melinda GlassSep 5, 2025
      To resolve a PID feedback offline fault in your INVT Inverter: * Check PID feedback signal wires because PID feedback may be offline. * Check PID feedback source because PID feedback source may disappear.

INVT Goodrive300-21 Series Specifications

General IconGeneral
Protection LevelIP20
Cooling MethodForced air cooling
Control MethodV/F control, vector control
Operating Temperature-10°C to +50°C
Overload Capacity150% rated current 60s; 180% rated current 3s
Braking UnitBuilt-in or external
CommunicationModbus
Protection FunctionsOvervoltage, undervoltage, overcurrent, overload, short circuit, overheating
Storage Temperature-20℃~+60℃
Ambient Humidity5%~95%, without condensation
Altitude≤1000m without derating