Production Specification and Performance
Rack Online 1-3k UPS User Manual 7
4. Product Specification and performance
4.1 Model Description
This manual is applicable to the following models:
L Model: Long backup time, S Model: Standard backup time
4.2 Product Specification and Performance
1. General Specification
Model 1K 2K 3K
Power Rating
1000VA/
800W
1000VA/
900W
2000VA/
1600W
2000VA/
1800W
3000VA/
2400W
3000VA/
2700W
Frequency (Hz)
50/60 50/60 50/60
Input
Voltage
110Vac~288Vac
Current
5.5A max. 11A max 16A max
Battery
Voltage
24VDC
36VDC
48VDC
72VDC
72VDC
96VDC
Numbers
2 3 4 6 6 8
Current
50A max
35A max
50A max
35A max
50A max
37A max
Output
Voltage
200V/208V/220V/230V/240V
Current
5/4.8/4.5/4.3/4.2A
10/9.6/9/8.6/8.4A
15/14.4/13.5/12.9/12.
6A
Dimension
(WxDxH) mm
438*426*86L/S
438*477*86L
438*477*173S
Weight
(kg)
Standard
11.5 13.5 21 25 27 31
Long 7 8 9.5
2. Electrical Performance
Input
Model Voltage Frequency Power Factor
1-3KVA Single-phase 40-70Hz >0.98(Full load)
Model No. Type
11xxS Standard model
11xxL Long backup model