Product Specification and Performance
True Online 6-20k UPS User Manual
10
3. Operating Environment
Temperature Humidity Altitude Storage temperature
0°C-40°C <95% <1000m 0°C-70°C
NOTICEIf the UPS is installed or used in a place where the altitude is above than 1000m,
the output power must be derated in use, please refer to the following:
Altitude (M) 1000 1500 2000 2500 3000 3500 4000 4500 5000
Derating Power 100% 95% 91% 86% 82% 78% 74% 70% 67%
Output
Voltage
Regulation
Power
Factor
Frequency
tolerance.
Distortion Overload capacity Crest ratio
±1% 0.9 lag
±0.1% of
normal
THD<1%
Full load
(Linear
Load)
110% load: transfers to
Bypass mode after 10
minutes
130% load: transfers to
Bypass mode after 1
minute
150% load :transfers to
Bypass mode after 0.5
minute and shutdown the
output after 1 minute
3:1
maximum

Questions and Answers: