iMars grid-tied solar inverters Display panel
47
Setting item
LCD display
Instruction
Set power
set power
P-Lmt
Mode
LmtPower
P.Factor
Limit Mode Invalid
Invalid
Auto
Manual
Limit Power
100%
Power Factor
Grid Tied Mode
Normal Mode
Power Factor 1.00
Input password
0000
The password is needed when enter
into the interface of “Set power”. Get
the password from the supplier if
necessary. There are 3 submenus:
P-Lmt Mode: invalid (limited power
function is invalid),auto ,manual (set
the limit of output value manually);
LmtPower: this function is only valid
when the P-Lmt Mode is manual, the
percentage is that of the rated power
and the setting range is from 10% to
100%; Power factor: includes
normal model (default value “1”),
current advanced mode and current
hysteresis mode and the setting rage
is -0.9-0.99.
Personal
Personal
MPP Start Volt
MPPT Volt
120V
Input password
0000
The password is needed when enter
into the personal interface. Get the
password from the supplier if
necessary. It can set MPPT starting
voltage from 120V to 160V under the
submenu of MPPT start volt.