Copyright © 2020 IoTecha Corp. All rights reserved.
25
Operating Current Selection
This EV charger contains a programmable maximum output current setting that allows the charger to
operate as a 10A – 80A charger. The installer must determine the intended output power setting in the
installation planning.
Note: The current selection must be performed by adjusting the rotary switch as detailed in “Rotary
switch Setting” on page 41.
Note: This device is considered as a “continuous load” device and as such the branch circuit must be
rated for 125% of the operating current