SECTION III
Operation
Page 3.22
BP+2.9X
11/95
Table 3.2 (continued)
Screen Message Description Corrective Action
sbs inhibit Static Bypass Switch inhibited Review other SBS alarms for
cause
sbs normal* Static Bypass Switch normal No action required
ups summary UPS summary alarm Review all alarms for cause
ups inhibit UPS inhibited Review all alarms for cause
ups normal* UPS in normal condition No action required
CPU normal* UPS processor normal No action required
UPS Powerup* UPS processor initialized No action required
EPO btn pshd EPO pushbutton pressed Complete UPS restart
procedure_is_required
EPO btn rlsd EPO pushbutton released Complete UPS restart
procedure_is_required
ctl pwr on~ Control power on No action required
ctl pwr off Control power off Turn on Control Power switch
rd wdog f It Rectifier watchdog fault Call Customer Service
rct hi shtdn Rectifier high shutdown Call Customer Service
dr rd wdog* Rectifier watchdog fault cleared No action required
pwrsply fail Power supply failure Call Customer Service
pwrsply nrml* Power supply normal No action required
ps inp fail Power supply input failure Call Customer Service
* Not an alarm condition.