SECTION III
Operation
Page 3.23
BP+2.9X
11/95
Table 3.2 (continued)
Screen Message Description Corrective Action
PS inp normal* Power supply input normal No action required
bat vlt nrml* Battery voltage normal No action required
sbs scr normal* Static bypass switch ----normal No action required
rct on util* Rectifier served by utility power No action required
sbs inp open Static bypass switch breaker open Follow Startup procedure to close
circuit breaker
sbs inp closed* Static bypass input switch or circuit
breaker closed
No action required
sbs out open Static bypass output switch is open Follow Startup procedure to close
switch
sbs out clsd* Static bypass output switch is closed No action required
xfer dsabld* Retransfer disabled No action required
inv no ovrld* Inverter drive no overload No action required
trnsnt overld lnverter drive transient overload Decrease load
lnv Overload Inverter drive overload Decrease load
ram normal* RAM is normal No action required
ph dial* Phone home dialout No action required
ph connect* Phone home connection established No action required
ph test Phone home test performed No action required
* Not an alarm condition.