APPENDIXB:DNP3COMMUNICATIONPROTOCOL
62 Measuringcentres
MC320,MC330,MC350&MC350H‐User’sManua
Object Request Response
Object
Number
Variation
Number
Description
Function
Codes(dec)
Qualifier
Codes(hex)
Function
Codes(dec)
Qualifier
Codes(hex)
60 1 CLASS0DATA 1 6
60 2 CLASS1DATA 1.22* 06
60 3 CLASS2DATA 1.22* 06
60 4 CLASS3DATA 1.22* 06
*onlyobject30
Tests:
Invalidstartoctets
Invalidprimaryfunctioncode
Invaliddestinationaddress
InvalidCRC
InvalidFCV