8.0 Specifications
Input
Voltage Model and Voltage Dependent (Table 8.1)
Current Model and Voltage Dependent (Table 8.1)
Frequency 60Hz +/- 2 Hz
Protection Input Circuit Breaker standard
Power Factor 0.5 lead to 0.5 lag
Output
Voltage Model and Voltage Dependent (Table 8.1)
Current Model and Voltage Dependent (Table 8.1)
Frequency 60Hz +/- 0.02 Hz crystal controlled during emergency mode
Overload 110 percent will generate overload fault
125% will generate overload shutdown
Transfer Time 2mS standard (User programmable to 50mS)
Output Distortion Less than 3% THD
Crest Factor 4X minimum on all models
Load Power Factor 0.5 lead to 0.5 lag
Output Types 1x Normally-On Standard – Normally-Off/Switched optional
Battery
Type Premium Long Life Valve-Regulated Lead Acid (VRLA)
Charger 3 rate with Temperature Compensation
Recharge Time 24 Hour recharge standard
Protection Automatic Low Voltage Disconnect (LVD) set at 1.67 VPC
Automatic restart upon utility return
Runtime 90 Minutes at 25 °C
DC Voltage Model and Voltage Dependent (Table 8.1)
DC Current Model and Voltage Dependent (Table 8.1)
Environmental
Operating Temp 20 to 30 °C
Storage Temp -20 to 70 °C (Electronics)
0 to 40 °C (Batteries)
Relative Humidity <95 % (non-condensing)
Physical
Cabinet NEMA Type 1 enclosure, 14 AWG powder painted CRS
Cooling Natural Convection – No fans during float charge
Forced Convection – Fans used during Inverter Mode of operation
Size/Weight Model and Voltage Dependent (Table 8.1)