Operation: C1SD, C1ST, and C1SL Versions
CENTRON Meter Technical Reference Guide 5-29
Errors
The table below shows how fatal and non-fatal errors affect R300CD RF
transmission.
The meter will transmit zeros for kWh and kW until it is programmed. For detailed programming
instructions, see the PC-PRO+ documentation. Also refer to the CENTRON R300CD Quick
Install Guide.
Error Error Code Error Type
Stops RF
Transmission
Low Battery 000001 Non-Fatal Yes
EEPROM 000010 Fatal Yes
Reverse Direction 007000 Non-Fatal No
Clock 010000 Non-Fatal Yes
Full Scale Overflow 100000 Non-Fatal Yes
TOU Error 020000 Non-Fatal Yes
Load Profile Error 030000 Non-Fatal Yes
Metrology Error 000004 Fatal Yes