7-3
12PHR-N
(1) Referring to the gure below, mark the location for the wall plugs and the piping hole.
• Recommended xing holes are marked in circle around the hole. (7 points)
• Make sure that the mounting plate is horizontally.
(2) Drill diameter 6.5 mm, depth 32 mm holes and t the wall
plug.
(3) Secure the mounting plate to the wall with the long screws
and check the stiffness.
(4) Drill a
piping hole with 70 mm
diameter concrete drill or a
hole saw with
a
5 mm down ward slant to the outside.
(5) Set the sleeve and caps.
260
23
40
8.5
798
88
71
71
329
94 138
0
0
88
32
mm
Length unit: mm
Center of wall hole:
Backward piping
Center of wall hole:
Leftward piping.
Outline of indoor unit
50 mm or more
(Unit size)
3 LONG SCREW
1 MOUNTING PLATE
1
Ceiling
(Unit size)
6.5
mm
2 WALL PLUG
2 WALL PLUG
Ø70
Ø65
Ø60
0
Piping gauge
Piping gauge
Stopper
Ø70
Ø65
Ø60
Determining hole position
1. Slide the piping gauge toward the piping
hole. Make sure that the stopper is t to
the “0” position on the mounting plate.
2. Mark the center of hole on the wall by
pushing the end of the piping gauge.
3. Replace the piping gauge
Wall
Indoor
Outdoor
Cut with a saw.
Cap
5 mm
Sleeve
(Downward to
outdoor
)
PLACING THE MOUNTING PLATE AND MAKING A PIPING HOLE
Mounting the indoor unit
For right side piping
(1) Pass the pipes and the drain hose through the piping
hole.
(2) Hook the unit onto the mounting plate.
(3) Pull the connecting cable into the indoor unit.
(4) Push the unit and apply the bottom hooks to the mount-
ing plate's support.
(5) Pull the bottom of the unit to check that the unit is xed in
place.
For left side piping
(1) Reverse the positions of the
drain hose and drain cap.
Refer to NOTES ON DRAIN
HOSE.
(2) Connect the pipes and connecting cable.
(3) Bind the pipes and connecting cable with tape.
(4) Set the them along the back of the unit, and attach the
piping holder.
(5) Pass the pipes, connecting cable and the drain hose
through the piping hole.
(6) Hook the unit onto the mounting plate.
(7) Push the unit and apply the bottom hooks to the mount-
ing plate's support.
(8) Pull the bottom of the unit to check that the unit is xed in
place.
Detaching the unit from the mounting plate
Push the “
“ marks at the bottom of the indoor unit and pull
the bottom of the unit. When the hooks are released from
the mounting plate, support the bottom of the unit and lift the
unit upwards.
1
3
2
4
5
Drain hose
2
Piping route
For directions 1, 2 ,4 and 5, cut out
the specic
zone without leaving
any sharp edge.
Plate
Plate
MOUNTING PLATE
Drain cap
Unit
Piping holder
Tape
Insert
Piping holder
Unit
Cut the plate along
notch.
Taping
Panel cover
Installation is easily achieved by removing the panel cover.
Removal
Remove the panel cover
by pushing arrow-marked
points.
Attachment
Fit the side of the panel cover
to the unit, and t in the bottom
of the panel cover to the unit.
Panel cover
Panel cover
Hook
MOUNTING PLATE
“ mark
SETTING UP THE INDOOR UNIT
12PHR-N_S530612PHRN.indd 3 2013/8/7 15:42:35