Alarms
6 720 643 409 (2010/03)
87
16.9.35 Short circuit on sensor E2x.T9 heat transfer
fluid in
Function: Activated when the sensor's value indicates a
temperature higher than 110 °C. T9 is calculated
according to the following formula: T9 = T8 - Compressor
x 7K + 0.07K x current output in operation.
Reset condition: The value of the sensor indicates
< 110 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has
disappeared.
16.9.36 Failure on sensor E2x.T10
Function: Activated when the sensor's resistance value
indicates a temperature lower than -20 °C. In the event
of a failure, T10 is set at a temperature calculated
according to the following formula: T10 = T11 +
Compressor x 3K.
Reset condition: The value of the sensor indicates
> -20 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has
disappeared.
16.9.37 Short circuit on sensor E2x.T10
Function: Activated when the sensor's value indicates a
temperature higher than 40 °C. In the event of a short
circuit, T10 is set at a temperature calculated according
to the following formula: T10 = T11 + Compressor x 3K.
Reset condition: The value of the sensor indicates
< 40 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has
disappeared.
16.9.38 Failure on sensor E2x.T11
Function: Activated when the sensor's value indicates a
temperature lower than -50 °C. In the event of a failure,
T11 is set at a temperature calculated according to the
following formula: T11 = T10 - Compressor x 3K.
Reset condition: The value of the sensor indicates
> -50 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has
disappeared.
16.9.39 Short circuit on sensor E2x.T11
Function: Activated when the sensor's value indicates a
temperature higher than 40 °C. In the event of a short
circuit, T11 is set at a temperature calculated according
to the following formula: T11 = T10 - Compressor x 3K.
Reset condition: The value of the sensor indicates
< 40 °C.
Category: H.
Alarm lamp/buzzer: Yes.
Restart: Automatic once the alarm cause has
disappeared.
16.9.40 Additional heat is now working at its highest
temperature
Function: The electric additional heat begins to be
stepped down. The warning is activated in additional
heat mode if the sensor T8 approaches the highest
temperature permitted for T8. The warning is blocked
during hot water peaks or extra hot water.
Reset condition: The warning is deactivated when the
sensor temperature falls sufficiently.
Category: K.
Alarm lamp/buzzer: No.
Restart: Automatic once the alarm cause has
disappeared.