Factory settings
6 720 643 409 (2010/03)
93
Installer F value
Access
level
General Anti-seizure mode Day of the week
Start time
Wednesday
12:00
1
1
Highest permitted flow temperature T1
Radiator/Underfloor 80/45 °C 1
Operating mode
1
Groundwater
Groundwater
Compressor start delay groundwater
No
15s
1
1
Time for reset of access level
180 min 1
Heat pump x capacity Select 1
Connected I/O boards Shows which circuit boards are
connected and their program version
1
Compressor working area Hot gas stop function activated No 1
Outdoor stop function activated
No 1
Circulation pumps Operation alternative heating circuit
pump G1
Continuous 1
Operation alternative heat carrier
pump G2
Automatic 1
Heat carrier pump G2 speed
40% 1
Operation alternative collector circuit
pump G3
Automatic 1
Screed drying Activate No 1
Heat source
Compressor 1
Remaining time for current step
1
Program settings
Flow temperature increase per heating
step
Number of days per heating step
Maximum flow temperature
Number of days with maximum
temperature
Flow temperature decrease per cooling
step
Number of days per cooling step
5,0K
1
45 °C
4
5.0K
1
1
1
1
1
1
1
Tab. 187Factory settings Installer
Additional heat F value
Access
level
Additional heat
general
Start delay 60 min 1
Allow additional heat timer during energy supply cut-off
Economy 1
Additional heat only
No 1
Ramp time when additional heat only
3 min 1
Block additional heat
No 1
Maximum outdoor temperature for additional heat
10 °C 1
Additional heat set point value E11.T1 offset
1,0K 1
Tab. 188Factory settings Additional heat