Installationsanvisning Janfire Flex - a
IA Brännare Flex-a R2 SV
Janfire 2009
15(19
)
Press the “Ext” button to decrease or “Dos” to increase time as shows in the figure. Press “Stop” to
save the new setting.
Om det önskas att brännare aldrig ska gå i underhåll ställer man tiden ner till 0. It is desired that the
burner should never go in the maintenance adjust time to 0.
60 min
50 min
40 min
30 min
0
Press “Stop” to save the new setting.
Exit Edit mode by pressing the Edit button again and then Edit/status diode light up again
3.8 The Functional Description
Start:
Set the boiler's thermostat on the desired temperature (recommended around 80°C). The water
temperature in the boiler should be lower so that the thermostat is active.
If burner starts when the water temperature is higher or even just below (the thermostat switched
off), the burner goes on standby for at least 35 min (safety time) if the thermostat still switched off.
It is better to adjust the temperature and restart the burner to avoid wait according to the following:
Press “STOPP” button. Cut off the power. Wait until all the diodes on the Panel goes off. Turn on
the power again. Raise the thermostat, and select power level.
When the power level is selected (except "M" mode) starts the fan and blows on max rpm for 10
min (security blow).
To skip the security wind to do this, follow these steps:
"STOPP" is active. Boiler thermostat shall be switched on. Press the "ext" until extern auger
stops(in the case that the level of the filler pipe is below the sensor and the diode on the sensor is
off).Press and hold the "ext" key and select any effect mode (not "M") and the burner starts without
safety blow.
Start-up: