CFL/LEDRATING IncandescentRATING NumberofDimmers HeatSink
150W 600W 1SwitchinSingleGang
Box
Full–Notabsremoved
125W 500W 2SwitchesinDouble
GangBox
Onetabremoved
(Inner)
100W 400W 3SwitchesinTriple
GangBox
Bothtabsremoved
ObserveImportantWiringInformation
Important:Thisswitchisratedforandintendedtoonlybeusedwithcopperwire.
Thehome’selectricalwiresmaybeattachedtothescrewterminalsorinsertedintotheholesinthe
backoftheswitchenclosureandclampedinplacebytighteningthescrewterminals.Alwaysfollowthe
recommendedwirestripl
engthswhenmakingwiringconnections.
Wiregaugerequirements
• Use 14AW Gorlargerwiressuitableforatleast80°Cforsupply(HOT),Load,Neutral,Groundand
Travelerconnections.
Wirestriplength:
• Forattachmenttoscrewterminals:Stripinsulation1in(25mm)
• Forattachmentusingtheen
closure’sholes:Stri
pinsulation5/8”(16mm)
ULspecifiesthatthetighteningtorqueforthescrewsis14Kgf‐cm(12lbf‐in).
SINGLESWITCHWIRING
1. Shutoffpowertothecircuitatfuseboxorcircuitbreaker.
2. Removewallplate.
!Warning:VerifypowerisOFFtosw
itchboxbefor
econtinuing.
3. Removetheswitchmounting screws.
4. Carefullyremovetheswitchfromtheswitchbox.DONOTdisconnectthewires.
5. Therearefivescrewterminalsontheswitch;thesearemarked
LINE(Hot)
Neutral
LOAD
GROUND
TRAVELER
TheTravelerterminalisonlyusedfor3‐wayor4‐waywiringandshouldremaininsulate
diftheswitchis
beinginstalle
dina2‐waysystem(oneswitch&oneload).Matchthesescrewterminalstothewires
connectedtotheexistingswitch.
6. Disconnect thewiresfromtheexistingswitch.
7. Connectthegree
norbarecoppergroundwiretotheGROUNDterminal.
8. ConnecttheblackwirethatgoestothelighttotheterminalmarkedLOAD.
9. Connecttheblackwirethatcomesfromtheelectricalservicepanel(Hot)totheterminalmarked
LINE.