EasyManua.ls Logo

Johnson Controls F4-XPM Series - Commissioning; Troubleshooting expansion modules; LED status and states

Johnson Controls F4-XPM Series
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 11: UI Current loop jumper positions
Setting the current loop jumper to the Enabled position,
connects an internal 100 ohm resistor across the UI
terminals, which maintains the 4-20 mA current loop
circuit even when power to the expansion module is
interrupted or off.
Important: Current Loop jumpers must be in the
Disabled (default) position for all UIs that are not set
up to operate as 4-20 mA analog inputs.
Important: A current loop jumper must be in the
Enabled position to maintain a closed 4-20 mA
current loop.
The following tables identify the current loop switches
associated with each UI on the XPM09090 and XPM04060
models.
Table 7: XPM09090 UI Inputs and jumper labels
Universal Input
label
Jumper label on circuit board
UI-1 J13
UI-2 J14
UI-3 J15
UI-4 J16
UI-5 J17
Table 7: XPM09090 UI Inputs and jumper labels
Universal Input
label
Jumper label on circuit board
UI-6 J18
UI-7 J19
Table 8: XPM04060 UI Inputs and jumper labels
Universal Input
label
Jumper label on circuit board
UI-1 J10
UI-2 J11
UI-3 J12
Setting up a local display
XPM models do not have an integral display, but can be
connected to an FX-DIS1710 Local Controller Display. For
detailed information about setting up and operating a
remotely connected FX-DIS1710 display, refer to the FX-
DIS Local Controller Display Technical Bulletin (LIT-12011666).
Commissioning
You commission expansion modules with the Controller
Configuration Tool (CCT) software using either Mobile
Access Portal (MAP) Gateway, a ZFR wireless dongle, or
in passthrough mode when connected to FX-SNC. Refer
to the Controller Tool Help (LIT-12011147) for detailed
information on commissioning expansion modules.
Troubleshooting expansion modules
Observe the Status LEDs on the front of the expansion module. Table 9 provides LED status indicator information for
troubleshooting the expansion module. To troubleshoot an integral or local controller display, refer to the FX-DIS1710
Local Controller Display Technical Bulletin (LIT-12011666).
LED status and states
Table 9: Status LEDs and description of LED states
LED label LED color Normal LED state Description of LED states
POWER Green On Steady
Off Steady = No Supply Power or the controller’s polyswitch/resettable fuse is
open. Check Output wiring for short circuits and cycle power to controller.
On Steady = Power Connected
FAULT Red Off Steady
Off Steady = No Faults
On Steady = Device Fault; no application loaded
Blink - 2 Hz = Startup in progress, not ready for normal operation
Rapid blink = SA Bus communications issue
SA/FC BUS Green Blink - 2 Hz
Blink - 2 Hz = Data Transmission (normal communication)
Off Steady = No Data Transmission
On Steady = Communication lost, waiting to join communication ring
EOL Amber
Off (Except on
terminating
devices)
On Steady = EOL switch in ON position
Off Steady = EOL switch in Off position
F4-XPM Expansion Modules Installation Guide 17

Related product manuals