16 FX20/60 Supervisory Controllers Installation Instructions
Table 4: Serial Port Pinouts
Pinout References Signal DB-9
Plug Pin
Base RS-485
Port (COM2)
Pinouts
DB-9 Plug (Male)
1
6
5
9
FIG:DB-9
DCD Data carrier detect 1
S + -
FIG:3pos
RXD Receive data 2
TXD Transmit data 3
DTR Data terminal ready 4
GND Ground 5
DSR Data set ready 6
RTS Request to send 7
CTS Clear to send 8
Not used on the FX20/FX60 9
RS-485 Port
An RS-485 non-isolated port uses a 3-position, screw
terminal connector and always operates as COM2.
Use shielded 18-22 AWG wire for this connector (refer
to the Telecommunications Industry
Association/Electronic Industries Alliance
[TIA/EIA-485 standard]). As shown in Table 4, the
screw terminals (from left to right) are shield, plus (+),
and minus (–).
USB Port (FX60 only)
A single USB port is on the top of the FX60.
Note: The USB port is for future use. Do not use the
port at this time.
Setup and Adjustments
Default Communication and Login Properties
The new FX20/FX60 are pre-configured with default
properties as defined in Table 5.
Table 5: FX20/FX60 Default Properties
Name Default Property
Internet Protocol (IP)
Address
192.168.1.149
Subnet Mask
255.255.255.0
Default Gateway
192.168.1.1
Remote User Name
jci
Remote Password
explorer
Powerup and Initial Checkout
Ensure that power wiring to the transformer is
complete before you proceed (see Power Wiring). See
Figure 6 for locations of the battery connector, status
LEDs, and barrel power connector. See Figure 7 for
location of the power connector on the DIN rail power
modules.
After you have completed all mounting and wiring
steps:
1. Connect the backup battery.
2. Apply power.
Check the status LEDs.

Related product manuals