Installation Instructions
Issue Date April 9, 2014
© 2014 Johnson Controls, Inc.
1
Part No. 24-10174-77, Rev. D www.johnsoncontrols.com
FX20/FX60 Supervisory Controllers
Installation Instructions
Application
The FX20 and FX60 are Web-based supervisory class
controllers in the Facility Explorer product family. The
FX20/FX60 manages networks of field controllers
using open communication protocols, such as N2,
L
ONWORKS®, and BACnet® protocols.
Figure 1: FX60 Supervisory Controller
North American Emissions Compliance
United States
This equipment has been tested and found to comply
with the limits for a Class A digital device pursuant to
Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful
interference when this equipment is operated in a
commercial environment. This equipment generates,
uses, and can radiate radio frequency energy and, if
not installed and used in accordance with the
instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in
a residential area is likely to cause harmful
interference, in which case the user will be required to
correct the interference at his/her own expense.
Canada
This Class (A) digital apparatus meets all the
requirements of the Canadian Interference-Causing
Equipment Regulations.
Cet appareil numérique de la Classe (A) respecte
toutes les exigences du Règlement sur le matériel
brouilleur du Canada.
Installation
Parts Included
Unpack the FX20/FX60 and accessories
(power module, option cards), if ordered. Inspect the
contents of the packages for damaged or missing
components. If damaged, notify the appropriate carrier
and return any damaged components for repair or
replacement.
Included in this package are the following items:
FX Supervisory Series controller
Hardware bag containing a grounding wire with
quick disconnect 0.187 in. (4.75 mm) female
connector.
Power module (if ordered). The power module
may be one of the following:
LP-FXPM24-0
(24 VAC, DIN rail mountable)
LP-FXPM263-0
(90-263 VAC, DIN rail mountable)
LP-FXPMUS-0
(90-240 VAC, with U.S. wall adapter)
LP-FXPMEU-0
(90-240 VAC, with European wall adapter)
LP-FXPMUK-0
(90-240 VAC, with U.K. wall adapter)
Communication cards (if ordered)
LP-FXLONFTT-1
LP-FXRS232-0
LP-FXRS485-0
LP-FXMDM-0
LP-FXWTC-0
Expansion Input/Output (NDIO) Modules
(if ordered)
LP-FXNDIO16-0
LP-FXNDIO34-0
LP-FXRIO16-0
Question and Answer IconNeed help?

Do you have a question about the Johnson Controls Facility Explorer FX20 and is the answer not in the manual?

Johnson Controls Facility Explorer FX20 Specifications

General IconGeneral
ModelFX20
Input Voltage24 VAC/DC
Communication ProtocolBACnet MS/TP, N2
Number of Inputs8 Universal Inputs (UI)
Operating Temperature32°F to 140°F (0°C to 60°C)
Storage Temperature-40 to 185°F (-40 to 85°C)
Communication PortsRS-485

Summary

Installation

Safety Precautions

Conductor and Wiring Requirements

Specifies conductor type and adherence to wiring regulations.

Environmental and Usage Guidelines

Advises against corrosive environments and proper usage.

Static Discharge Precautions

Preventing Static Discharge Damage

Guidance on preventing static discharge damage to electronic components.

Mounting

Physical Mounting Considerations

Details on the physical aspects of mounting the unit.

DIN Rail Mounting Instructions

Step-by-step guide for mounting components on a DIN rail.

Expansion Options

Mounting Option Cards

Wiring Connections Procedure

Instructions for connecting communication and power wiring for option cards.

Earth Grounding Procedure

Steps for properly grounding the unit and accessory modules.

Power Wiring

Wiring LP-FXPM24-0 Power Module

LP-FXPM263-0 Line Voltage Power Module

Electric Shock Hazard Warning

Critical warning about electric shock hazards during installation.

Communications Wiring

Setup and Adjustments

Default Configuration Properties

Pre-configured network and login settings for the FX20/FX60.

Powerup and Initial Checkout

Connecting the Backup Battery

Operation Mode

Checking System Status via LEDs

How to interpret the system status using the unit's LEDs.

Status LED Indicators

Heartbeat LED Status

Status LED Functionality

Niagara^x Software Setup

IP Address Configuration

Restoring a Backed Up Station

Required Battery Maintenance

Replacing an FX20;FX60 Unit

Static Discharge Precautions (Unit Replacement)

Static discharge warning before handling circuit boards during unit replacement.