EasyManua.ls Logo

Johnson Controls Facility Explorer FX20 - Page 4

Johnson Controls Facility Explorer FX20
22 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 FX20/60 Supervisory Controllers Installation Instructions
Table 1: Accessory Module Details
Model Description Notes
LP-FXPM24-0
Power module for FX20/FX60
24 VAC/DC, DIN rail mountable
Install only one power module per FX20/FX60, regardless
of type.
LP-FXPM263-0
Power module for FX20/FX60
90-263 VAC, DIN rail mountable
Install only one power module per FX20/FX60, regardless
of type.
LP-FXNDIO16-0
16 channel input/output module for
FX20/FX60, DIN rail mountable
Provides the following I/O points:
8 Universal Inputs (UIs)
4 Digital Outputs (DOs), Single Poll Single Throw
(SPST) relay type
4 Analog Outputs (AOs) (0-10 VDC)
Up to four (maximum) NDIO16 accessory modules are
supported.
LP-FXNDIO34-0
34 channel input/output module for
FX20/FX60, DIN rail mountable. In
addition, the NDIO34 provides power to
the attached FX20/FX60, using an
externally supplied 24 VAC transformer or
24 VDC power supply.
Provides the following I/O points:
16 Universal Inputs (UIs)
10 Digital Outputs (DOs), SPST relay type
8 Analog Outputs (AOs) (0-10 VDC)
One NDIO34 plus up to 2 additional NDIO16 modules are
supported. Do not power the NDIO34 if using a separate
wall plug power module.
LP-FXRIO16-0
16 channel remote input/output Provides the following I/O points:
8 Universal Inputs (UIs)
4 Form A Relay Outputs
4 1-10 VDC Analog Outputs
Up to 4 FXRIO10 modules supported on FX20
Up to 16 FXRIO16 modules supported on FX60

Related product manuals