Installing the NAE/NIE Technical Bulletin 15
Do add additional devices to the enclosure as long as the
temperature of the processor is maintained below 77°C (171°F) per
the readout of the processor chip’s embedded temperature sensor.
(Read the temperature in the Diagnostics tab of the device object.
See the NAE Help system for more information on diagnostics.)
Note: No general guidance can be given about the number of
heat-dissipating devices that can be mounted in a panel with the NAE.
The acceptable combinations of devices and mounting locations can be
determined only by testing the installation.
Mounting Space
Figure 9 shows the mounting space required for the NAE.
303 mm
(11.9 in.)
408 mm
(16.1 in.)
148 mm
(5.8 in.)
mountspace
DIN Rail
125 0.5 mm
(4.9 0.02 in.)
N2- B
N2-
A
POWER
+
-
REF
S
N2
+
-
REF
S
N2
+
NC
-
POWER
ETHERNET
10
/
LINK
100
/
LINK
N2
A
N2B
PEER COM
RUN
24 V
A
C
B
A
TT F
A
ULT
GENL F
A
ULT
SERI
A
LB
SERI
A
L
A
USB A
USB B
ETHERNET MODEM
SYSTEM
RE-BOOT
NAE
R
ET SY
B A T T E R Y
DIN Rail
32 mm
(1.3 in.)
30 mm
(1.2 in.)
Figure 9: NAE Mounting Space
Correct Mounting Orientations
Wall and Cabinet/Enclosure Mount
See Figure 10 for correct wall and cabinet/enclosure mounting
orientations.
naewallmount
BEST
L
O
N
L
O
N
A
L
O
N
B
S
H
I
E
L
D
N
2
-
B
N
2
-
A
P
O
W
E
R
+
-
R
E
F
S
N
2
+
-
R
E
F
S
N
2
+
N
C
-
S
E
R
I
A
L
B
S
E
R
I
A
L
A
U
S
B
A
U
S
B
B
OK
Figure 10: Wall and Cabinet/Enclosure Mount Orientation

Related product manuals