505429-JTG-L-0512
Johnson Controls Unitary Products 11
J07 - 20NC and J10 - 20ND Indoor Unit Physical Data
Component
Models
J07NC J10NC J10ND J15NC J15ND J20NC J20ND
Nominal Tonnage 7 1/2 10 10 15 15 20 20
DIMENSIONS (inches)
Length
56.0 56.0 56.0 74.5 74.5 98.5 98.5
Width
30.0 30.0 30.0 33.0 33.0 30.0 30.0
Height
65.0 65.0 65.0 75.0 75.0 65.0 65.0
WEIGHTS (lb)
Unit Shipping
526 573 575 796 796 938 938
Unit Operating With
Standard Motor and Drive
498 539 541 764 764 873 873
High Static Motor and Drive
500 550 552 792 792 903 903
INDOOR BLOWER (Forward Curve)
Diameter x Width 12 x 12 15 x 15 15 x 15 18 x 18 18 x 18 15 x 15 15 x 15
Quantity 1 111122
INDOOR COIL
Face area (Sq. Ft.) 10.6 10.6 10.6 18.3 18.3 20.0 20.0
Rows 3 443444
Fins per inch 15 15 15 15 15 15 15
Tube diameter 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Circuitry Type Interlaced Interlaced Interlaced Interlaced Interlaced Interlaced Interlaced
Refrigerant Control TXV TXV TXV TXV TXV TXV TXV
SYSTEM DATA
No. Refrigeration Circuits 1 121212
Suction Line OD (in.) 1 1/8 1 3/8 1 1/8 1 5/8 1 3/8 1 5/8 1 3/8
Liquid Line OD (in.) 5/8 7/8 5/8 7/8 5/8 7/8 7/8
FILTERS
Size and Quantity Per
Model (In.)
16 x 25 x 2 4 4 4 --- --- 8 8
20 x 24 x 2 --- --- --- 6 6 --- ---
FACE AREA (SQ. FT.) 11.1 11.1 11.1 20.0 20.0 22.2 22.2
Size and Quantity Per
Model (In.)
16 x 25 x 4 4 4 4 --- --- 8 8
20 x 24 x 4 --- --- --- 6 6 --- ---
FACE AREA (SQ. FT.) 11.1 11.1 11.1 18.0 18.0 22.2 22.2