EasyManua.ls Logo

Johnson Controls R-410A - Electrical Data

Johnson Controls R-410A
128 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
505429-JTG-L-0512
74 Johnson Controls Unitary Products
Electrical Data
Electrical Data For Outdoor Models
Electrical Data - Outdoor Unit - AC Without Powered Convenience Outlet
Model
Compressors Outdoor Fan Motor Pwr Conv Outlet
Minimum
Circuit
Ampacity
1
Maximum
Fuse Size
(A)
2
Power
Supply
Qty
RLA
(each)
MCC
(each)
LRA
(each)
Power
Supply
HP Qty
FLA
(each)
FLA
J07YC
208/230-3-60 1 25.0 39 164 208/230-1-60 1/3 2 2.1 - 35.5 45
460-3-60 1 12.2 19 100 460-1-60 1/3 2 1.2 - 17.6 25
575-3-60 1 9.0 14 78 575-1-60 1/3 2 0.9 - 13.1 20
J10YC
208/230-3-60 2 18.1 28.3 137 208/230-1-60 3/4 2 3.0 - 46.8 60
460-3-60 2 9.0 14.0 62 460-1-60 3/4 2 1.6 - 23.5 30
575-3-60 2 6.8 10.6 50 575-1-60 3/4 2 1.4 - 18.0 20
J10YD
208/230-3-60 2 17.3 27 123 208/230-1-60 3/4 2 3.0 - 45.0 60
460-3-60 2 9.6 15 70 460-1-60 3/4 2 1.6 - 24.8 30
575-3-60 2 7.7 12 53 575-1-60 3/4 2 1.4 - 20.0 25
J12YC
208/230-3-60 2 22.4 35 149 208/230-1-60 3/4 2 3.0 - 56.5 70
460-3-60 2 10.6 17 75 460-1-60 3/4 2 1.6 - 27.1 35
575-3-60 2 7.7 12 54 575-1-60 3/4 2 1.4 - 20.0 25
J12YD
208/230-3-60 2 23.1 36 160 208/230-1-60 3/4 2 3.0 - 58.0 80
460-3-60 2 12.2 19 87 460-1-60 3/4 2 1.6 - 30.7 40
575-3-60 2 8.7 14 62 575-1-60 3/4 2 1.4 - 22.3 30
J15YC
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 - 64.7 80
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 - 32.2 40
575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 - 24.0 30
J15YD
208/230-3-60 2 25.0 39 164 208/230-1-60 1/3 4 2.1 - 64.7 80
460-3-60 2 12.2 19 100 460-1-60 1/3 4 1.2 - 32.2 40
575-3-60 2 9.0 14 78 575-1-60 1/3 4 0.9 - 24.0 30
J20YC
208/230-3-60 2 30.1 47 225 208/230-1-60 3/4 4 3.0 - 79.8 100
460-3-60 2 16.7 26 114 460-1-60 3/4 4 1.6 - 44.0 60
575-3-60 2 12.2 19 80 575-1-60 3/4 4 1.4 - 32.9 45
J20YD
208/230-3-60 2 30.1 47 225 208/230-1-60 3/4 4 3.0 - 79.8 100
460-3-60 2 16.7 26 114 460-1-60 3/4 4 1.6 - 44.0 60
575-3-60 2 12.2 19 80 575-1-60 3/4 4 1.4 - 32.9 45
J25YC
208/230-3-60 2 48.1 75 245 208/230-1-60 3/4 4 3.0 - 120.3 150
460-3-60 2 18.6 29 125 460-1-60 3/4 4 1.6 - 48.3 60
575-3-60 2 14.7 23 100 575-1-60 3/4 4 1.4 - 38.5 50
1
Based on three, 75°C insulated copper conductors in conduit and ambient of 30°C.
2
Maximum fuse or maximum circuit breaker (HACR type per NEC).
Refer to NEC/NFPA No. 70, Articles 440-11, 12 for information on minimum disconnect sizing.